Functional description
© 2006 ABB STOTZ-KONTAKT GmbH
43
ABB i-bus
®
EIB / KNX
3.4.7
“Status” parameter
window
Fig. 14:
“Status” parameter window
In the
Status
parameter window, the behaviour of the status and
communication objects is defined.
On change of selected device send status on/off and value
Option:
Yes
No
With the setting „yes“ the switching status and the brightness status are
send if the DALI device is select with the object „Select device“ With the
setting „no“ the status must read actively with a separate command.
On change of selected device send Fault Lamp and Fault Ballast
Option:
Yes
No
With the setting „yes“ the status fault lamp and fault ballast are send if
the DALI device is select with the object „Select device“ With the setting
„no“ the status must read actively with a separate command.
Send telegram "Fault Ballast"
Option:
only on read request
on change of status
With the setting "only on read request", the object value "Telegr. fault
ballast" can only be read when requested. For the parameter setting "on
change of status", the current status is sent independently via the
communication object when changed.