Functional description
© 2006 ABB STOTZ-KONTAKT GmbH
55
ABB i-bus
®
EIB / KNX
3.5.3
Lightscene communication
objects
Fig. 18
Communication objects for “Recall Lightscene x/y”
15 lightscenes can be activated via the parameter setting. The scenes can
be defined by the ETS entries or set individually by the user according to
personal requirements via the individual object. It is possible for each scene
to disable overwriting of the brightness values during an ETS download. The
individually set brightness values of the lightscene are hereby retained
during an ETS download.
There are separate communication objects for retrieving or saving the 15
lightscenes. There is a further 8-bit communication object available, with
which each one of the 15 lightscenes can be stored or retrieved via an 8-bit
code.
No.
Function
Object name
Data type
Flags
36
Recall scene
Scene 1/2
1 bit (EIS 1)
DPT 1.022
C, W
37
Recall scene
Scene 3/4
1 bit (EIS 1)
DPT 1.022
C, W
38
Recall scene
Scene 5/6
1 bit (EIS 1)
DPT 1.022
C, W
39
Recall scene
Scene 7/8
1 bit (EIS 1)
DPT 1.022
C, W
40
Recall scene
Scene 9/10
1 bit (EIS 1)
DPT 1.022
C, W
41
Recall scene
Scene 11/12
1 bit (EIS 1)
DPT 1.022
C, W
42
Recall scene
Scene 13/14
1 bit (EIS 1)
DPT 1.022
C, W
43
Recall scene
Scene 15
1 bit (EIS 1)
DPT 1.022
C, W
Lightscene X/Y Recall scene [EIS 1; 1-bit switching]:
The scenes are retrieved via this
object. On receipt of a telegram, channels which are assigned to the scene are set to the
stored or parameterised brightness values. The communication objects are only visible if the
scenes have been activated in the
Scenes
parameter window. The scene can consist of
devices from channel A and B.
Telegram value
“0”: Recall scene X
"1": Recall scene Y
Table 9
Communication objects for “Recall Lightscene x/y”"