Modifications reserved
Page 23/26
16.3
Single input feed (standard version)
16.3.1
Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected.
16.3.2
Cable sections
Frame type
Load
in kW
Input 3 x 400 V/230 V
Output 3 x 400 V/230
V @ cosphi 1.0
Battery
Fuse A
(Agl/CB)
Cable A (mm
2
)
(IEC 60950-1)
Max. input current
with battery charging [A]
Cable D (mm
2
)
(IEC 60950-1)
I nom
[A]
Fuse E
+ / N / -
(Agl/CB)
Cable E (mm
2
)
for CBAT UPScale 120
or 200 ONLY
+ / N / -
Com.
battery
Sep.
Battery
UPScale ST 40
40
3 x 80 A
5 x 16
68 A
5 x 16
58 A
NOT ALLOWED
UPScale ST 60
60
3 x 125 A
5 x 35
102 A
5 x 35
87 A
UPScale ST 80
80
3 x 160 A
5 x 50
136 A
5 x 50
116 A
3 x 224 A*1
3 x 95 *1
4x(3x10)
UPScale ST120
120
3 x 224 A
4 x 95+1 x 50
(PE)
208 A
5 x 70
174 A
3 x 300 A*1
3 x 150 *1
6x(3x10)
UPScale ST 200
200
3 x 350 A
5 x 185
333 A
5 x 185
290 A 3 x 450 A *1
3x(2x95)*1
5x(3x25)
*1 only valid for common battery use
Summary of Contents for DPA UPScale ST120
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...