Modifications reserved
Page 24/26
16.4
Dual input feed (optional version)
16.4.1
Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected
16.4.2
Cable sections
Frame
type
UPScale
ST
Load
in
kW
Input 3 x 400 V/230 V
Bypass 3 x 400 V/230 V Output 3 x 400 V/230 V
@ cosphi 1.0
Battery
Fuse B
(Agl/CB)
Cable B (mm
2
)
(IEC 60950-1)
Max.
input
current
with
battery
charging
[A]
Fuse C
(Agl/CB)
Cable C
(mm
2
)
(IEC
60950-1)
Cable D
(mm
2
)
(IEC
60950-1)
I nom
[A]
Fuse E
+/N/-
(Agl/CB)
Cable E (mm
2
)
for CBAT UPScale 120 or
200 ONLY
+ / N / -
Com.
battery
Sep.
battery
40
40
3 x 80 A
5 x 16
68 A
3 x 80A
4 x 16
5 x 16
58 A
NOT ALLOWED
60
60
3 x 125 A
5 x 35
102 A
3 x 125A
4 x 35
5 x 35
87 A
80
80
3 x 160 A
5 x 50
136 A
3 x 160A
4 x 50
5 x 50
116 A
3 x 224
A*1
3 x 95 *1
4 x (3 x 10)
120
120
3 x 224 A
4 x 95+1 x 50
(PE)
208 A
3 x 224A
4 x 95
5 x 70
174 A
3 x 300
A*1
3 x 150 *1 6 x (3 x 10)
200
200
3 x 350 A
5 x 185
333 A
3 x 350 A
4 x 185
5 x 185
290 A
3 x 450
A*1
3x(2x95)*1 5 x (3 x 25)
*1 only valid for common battery use
Summary of Contents for DPA UPScale ST120
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...