Modifications reserved
Page 7/26
4
Environmental characteristics
The following data declarations are valid for DPA UPScale M10 and M20 modules.
Ambient temperature range
°C
0 - 40
Relative humidity range
< 95% (non-condensing)
Installation altitude with full rating ASL
m
1000
Derating power factor for installation
altitude above 1000 m ASL
m
0.95 @ 1500 m
0.91 @ 2000 m
0.86 @ 2500 m
0.82 @ 3000 m
Storage temperature
°C
-25 - +70
The following are recommended for internal and external batteries:
Ambient temperature range
°C
20 – 25
Battery storage time at ambient
temperature
Max. 6 months
5
Input characteristics
Module type
UPScale M10
UPScale M20
Module rated power
kW
10
20
Nominal input voltage
V
3 x 380/220 V+N, 3 x 400 V/230 V+N, 3 x 415/240 V+N
Input voltage tolerance
(ref to 3 x 400/230 V)
for loads in%:
V
(-20%/+15%) 3 x 320/184 V to 3 x 460/265 V for <100% load
(-26%/+15%) 3 x 296/170 V to 3 x 460/265 V for < 80% load
(-35%/+15%) 3 x 260/150 V to 3 x 460/265 V for < 60% load
Input frequency
Hz
35 – 70
Input power factor
-
0.99 @ 100% load
Inrush current
A
max. In
Rated short-time withstand
current (Icw)
kA
10 for 1.5 seconds
AC power distribution system: TN-S, TN-C, TN-C-S, TT, 3ph + N
Total harmonic
distortion (THDi)
%
< 4.5
< 3.0
Max. input power with rated
output power (cosphi = 1.0),
rated input voltage and
charged battery per module
kW
10.5
21
Max. input current with rated
output power (cosphi = 1.0),
rated input voltage and
charged battery per module
A
15.2
30.4
Max. input power with rated
output power (cosphi = 1.0),
rated input voltage and
discharged battery per module
kW
11.5
23
Max. input current with rated
output power (cosphi = 1.0),
rated input voltage and
discharged battery per module
A
16.6
33.3
Bypass input rated voltage
(-/+15%) 3 x 400 V or 196 V to 264 V ph-N
Summary of Contents for DPA UPScale ST120
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...