Modifications reserved
Page 67/79
8
Options
8.1
System
8.1.1
Backfeed protection
The UPS backfeed protection prevents any hazardous voltage or energy from being present on the
UPS input AC terminals after interruption of the input AC power.
The backfeed protection is implemented in the DPA UPScale ST by internal backfeed protection
contactors (K1 and K2) as shown in the wiring diagram below.
Fig 8.1.1-1: Backfeed protection
K1
Mains backfeed contactor
(option)
In the event of an AC failure, prevents the occurrence of any
hazardous voltage at the rectifier mains terminal due to
backfeed from the power modules sourced by the battery
K2
Bypass backfeed contactor
(option)
In the event of an AC failure, prevents the occurrence of any
hazard voltage at the bypass input terminal due to backfeed
from the power modules sourced by the battery
Order Number
04-0727
Backfeed protection ST40
04-0728
Backfeed protection ST60
04-0729
Backfeed protection ST80
04-0730
Backfeed protection ST120
04-3229
Backfeed protection ST200
Summary of Contents for DPA UPScale ST120
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...