Modifications reserved
Page 75/79
9.2.3
Fault identification and rectification
The major alarm conditions that will be encountered are:
ALARM CONDITION
MEANING
SUGGESTED SOLUTION
MAINS RECT. FAULT
Mains power supply is
outside prescribed tolerance.
The input power to the UPS is
too low or missing.
If site power appears to be
OK, check the input circuit
breakers, etc. supplying the
UPS.
MAINS BYP FAULT
Mains power supply is
outside prescribed tolerance.
The input power to the UPS is
too low or missing.
If site power appears to be
OK, check the input circuit
breakers, etc. supplying the
UPS.
OUTPUT SHORT
There is a short circuit at the
output of the UPS (on the
load side).
Check all output connections
and repair as required.
OVERLOAD
Load exceeds the UPS rated
power.
Identify which piece of
equipment is causing the
overload and remove it from
the UPS.
Do not connect laser printers,
photocopiers, electric heaters,
kettles, etc. to the UPS.
TEMPERATURE HIGH
UPS temperature has
exceeded the allowed value.
Check that the ambient
temperature of the UPS is less
than 40° C.
If the ambient temperature is
normal, call the certified
service center for assistance.
INV. PHASE FAULT
Inverter is faulty.
Call the certified service
center for assistance.
SYNCHRON. FAULT
The inverter and mains are
not synchronized.
The frequency of the input
voltage to the UPS is outside
operational limits and the UPS
static bypass has been
temporarily disabled.
BATTERY IN DISCHARGE
Battery is near end of
autonomy.
Shutdown load connected to
the UPS before the UPS
switches itself off to protect its
batteries.
MANUAL BYP IS CLOSED
Maintenance bypass closed.
Load supplied by mains.
This alarm is only displayed if
the UPS is on maintenance
bypass.
In case of alarms not included in the list above, please contact the nearest certified service center for
assistance.
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...