112
ACH550-UH User’s Manual
3609
STOP DAY 2
1…7
1
1
Defines timer 2 weekly stop day.
• See parameter 3605
3610
START TIME 3
00:00:00…23:59:58
2 s
12:00:00
Defines timer 3 daily start time.
• See parameter 3602
3611
STOP TIME 3
00:00:00…23:59:58
2 s
12:00:00
Defines timer 3 daily stop time.
• See parameter 3603
3612
START DAY 3
1…7
1
1
Defines timer 3 weekly start day.
• See parameter 3604
3613
STOP DAY 3
1…7
1
1
Defines timer 3 weekly stop day.
• See parameter 3605
3614
START TIME 4
00:00:00…23:59:58
2 s
12:00:00
Defines timer 4 daily start time.
• See parameter 3602
3615
STOP TIME 4
00:00:00…23:59:58
2 s
12:00:00
Defines timer 4 daily start time.
• See parameter 3603
3616
START DAY 4
1…7
1
1
Defines timer 4 weekly start day.
• See parameter 3604
3617
STOP DAY 4
1…7
1
1
Defines timer 4 weekly stop day.
• See parameter 3605
3622
BOOST SEL
-6…6
1
0
Selects the source for the boost signal.
0 = NOT SEL- Boost signal is disabled.
1 = DI1-Defines DI1 as the boost signal.
2…6 = DI2…DI6 – Defines DI2…DI6 as the boost signal.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the boost signal.
-2…-6 = Defines an inverted digital input DI2…DI6 as the boost signal.
3623
BOOST TIME
00:00:00-23:59:58
2 s
00:00:00
Defines the boost ON time. Time is started
when boost sel signal is released. If parameter
range is 01:30:00, then boost is active for 1
hour and 30 minutes after activation DI is
released.
Group 36: Timer Functions
Code Description Range
Resolution
Default
S
Boost active
Activation DI
Boost time