Group 51: Ext Comm Module
This group defines set-up variables for a fieldbus adaptor (FBA) communication
module. For more information on these parameters, refer to the user’s manualation
supplied with the FBA module.
Group 51: Ext Comm Module
Code Description Range
Resolution
Default
S
5101
FBA TYPE
-
1
0
Displays the type of the connected fieldbus adapter module.
0 =
NOT
DEFINED
– Module not found, or not properly connected, or parameter 9802 is not set to 4 (ex
T
FBA
).
1 =
PROFIBUS
-
DP
–
16 =
INTERBUS
–
21 =
LONWORKS
–
32 =
CANOPEN
–
37 =
DEVICENET
–
64 =
MODBUS
PLUS
–
101 =
CONTROLNET
–
128 =
ETHERNET
–
5102
…
5126
FB PAR 2…FB PAR 26
0...65535
1
0
For more information on these parameters, refer to the user’s manual supplied with the FBA module.
5127
FBA PAR REFRESH
0, 1
1
0
Validates any changed fieldbus parameter settings.
• After refreshing, the value reverts automatically to DONE.
5128
FILE CPI FW REV
0000…FFFF hex
1
0000 hex
Displays the CPI firmware revision of the drive’s fieldbus adapter configuration file. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example:
107 = revision 1.07
5129
FILE CONFIG ID
0000…FFFF hex
1
0000 hex
Displays the revision of the drive’s fieldbus adapter module’s configuration file identification.
• File configuration information is drive application program-dependent.
5130
FILE CONFIG REV
0000…FFFF hex
1
0000 hex
Contains the revision of the drive’s fieldbus adapter module configuration file.
Example:
1 = revision 1
5131
FBA STATUS
0…6
1
0
Contains the status of the adapter module.
0 =
IDLE
– Adapter not configured.
1 =
EXEC
.
INIT
– Adapter is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the adapter and the drive.
3 =
CONFIG
ERROR
– Adapter configuration error.
• The major or minor revision code of the adapter’s CPI firmware revision differs from that stated in the drive’s
configuration file.
4 =
OFF
-
LINE
– Adapter is off-line.
5 =
ON
-
LINE
– Adapter is on-line.
6 =
RESET
– Adapter is performing a hardware reset.
5132
FBA CPI FW REV
0000…FFFF hex
1
0000 hex
Contains the revision of the module’s CPI program. Format is xyz where:
• x = major revision number
• y = minor revision number
• z = correction number
Example: