174
ACH550-UH User’s Manual
Serial Communication – EFB
1.
RATED
SPEED
is a percent of maximum frequency (parameter 2008) if the drive is in scalar mode,
and is a percent of maximum speed (parameter 2002) in speed mode.
N2 Binary Input Objects
The following table lists all of the N2 Binary Input objects defined for the ACH550
drive.
AI9
MEGAWATT HOURS
0141
1
MWh
0…999
AI10
RUN TIME
0114
1
H
0…9999
AI11
DC BUS VOLTAGE
0107
1
V
0…999
AI12
OUTPUT VOLTAGE
0109
1
V
0…999
AI13
PRC PID FEEDBACK
0130
10
%
0…100
AI14
PRC PID DEVIATION
0132
10
%
0…100
AI15
EXT PID FEEDBACK
0131
10
%
0…100
AI16
EXT PID DEVIATION
0133
10
%
0…100
AI17
LAST FAULT
0401
1
fault code
AI18
PREV FAULT
0402
1
fault code
AI19
OLDEST FAULT
0403
1
fault code
AI20
AI 1 ACTUAL
0120
10
%
0…100
AI21
AI 2 ACTUAL
0121
10
%
0…100
AI22
AO 1 ACTUAL
0124
10
mA
0…20
AI23
AO 2 ACTUAL
0125
10
mA
0…20
AI24
MOTOR TEMP
0145
1
°
C
0…200
AI25
REVOLUTION CNT
0142
1
MREV
0…32767
N2 Binary Inputs:
Number
Object
Drive Parameter
Range
BI1
STOP/RUN
Status Word
0 = Stop, 1 = Drive Running
BI2
FORWARD/REVERSE
Status Word
0 = Forward, 1 = Reverse
BI3
FAULT STATUS
Status Word
0 = OK, 1 = Drive Fault
BI4
RELAY 1 STATUS
0122 (bit mask 04)
0 = Off, 1 = On
BI5
RELAY 2 STATUS
0122 (bit mask 02)
0 = Off, 1 = On
BI6
RELAY 3 STATUS
0122 (bit mask 01)
0 = Off, 1 = On
BI7
RELAY 4 STATUS
0123 (bit mask 04)
0 = Off, 1 = On
BI8
RELAY 5 STATUS
0123 (bit mask 02)
0 = Off, 1 = On
BI9
RELAY 6 STATUS
0123 (bit mask 01)
0 = Off, 1 = On
BI10
INPUT 1 STATUS
0118 (bit mask 04)
0 = Off, 1 = On
BI11
INPUT 2 STATUS
0118 (bit mask 02)
0 = Off, 1 = On
BI12
INPUT 3 STATUS
0118 (bit mask 01)
0 = Off, 1 = On
BI13
INPUT 4 STATUS
0119 (bit mask 04)
0 = Off, 1 = On
N2 Analog Inputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range