186
ACH550-UH User’s Manual
Serial Communication – EFB
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets { } may be unbundled at the field panel.
66
LDO
SPD OUT MIN
0
PCT
0.1
0
-
-
67
LDO
SPD OUT MAX
1000
PCT
0.1
0
-
-
{68}
LDO
FLN LOC CTL
AUTO
-
1
0
FLN
AUTO
{69}
LDO
FLN LOC REF
AUTO
-
1
0
FLN
AUTO
{70}
LDI DI
1
ACTUAL
OFF
-
1
0
ON
OFF
{71}
LDI DI
2
ACTUAL
OFF
-
1
0
ON
OFF
{72}
LDI DI
3
ACTUAL
OFF
-
1
0
ON
OFF
{73}
LDI DI
4
ACTUAL
OFF
-
1
0
ON
OFF
{74}
LDI DI
5
ACTUAL
OFF
-
1
0
ON
OFF
{75}
LDI DI
6
ACTUAL
OFF
-
1
0
ON
OFF
{76}
LDI
RO 1 ACTUAL
OFF
-
1
0
ON
OFF
{77}
LDI
RO 2 ACTUAL
OFF
-
1
0
ON
OFF
{78}
LDI
RO 3 ACTUAL
OFF
-
1
0
ON
OFF
{79}
LDI
RO 4 ACTUAL
OFF
-
1
0
ON
OFF
{80}
LDI
RO 5 ACTUAL
OFF
-
1
0
ON
OFF
{81}
LDI
RO 6 ACTUAL
OFF
-
1
0
ON
OFF
{82}
LAI
AI 1 ACTUAL
0
PCT
0.1
0
-
-
{83}
LAI
AI 2 ACTUAL
0
PCT
0.1
0
-
-
{84}
LAI
AO 1 ACTUAL
0
MA
0.1
0
-
-
{85}
LAI
AI 2 ACTUAL
0
MA
0.1
0
-
-
{86}
LDI
OK.ALARM
OK
-
1
0
ALARM
OK
{87}
LDI
OK.MAINT
OK
-
1
0
MAINT
OK
{88}
LAI
ALARM WORD 1 -
-
1
0
-
-
{89}
LAI
ALARM WORD 2 -
-
1
0
-
-
{90}
LAI
LAST FAULT
-
-
1
0
-
-
{91}
LAI
PREV FAULT 1
-
-
1
0
-
-
{92}
LAI
PREV FAULT 2
-
-
1
0
-
-
{93}
LDI
OK.FAULT
OK
-
1
0
FAULT
OK
{94}
LDO
RESET FAULT
NO
-
1
0
RESET
NO
{95}
LAO
MBOX PARAM
-
-
1
0
-
-
{96}
LAO
MBOX DATA
-
-
1
0
-
-
{97}
LDO
MBOX READ
DONE
-
1
0
READ
DONE
{98}
LDO
MBOX WRITE
DONE
-
1
0
WRITE
DONE
{99}
LAO
ERROR STATUS
-
-
1
0
-
-
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)