ACH550-UH User’s Manual
Technical Data
Emergency Stop Devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
•
Generate an emergency stop of the motor.
•
Separate the drive from dangerous potential.
Input Power Cables/ Wiring
Input wiring can be either:
•
A four conductor cable (three phases and ground/protective earth) routed through
conduit.
•
Four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive’s load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see "Drive’s Power Connection Terminals" on page
231).
The table below lists copper and aluminum cable types for different load currents.
These recommendations apply only for the conditions listed at the top of the table.
IEC
NEC
Based on:
• EN 60204-1 and IEC 60364-5-2/2001
• PVC insulation
• 30 °C (86 °F) ambient temperature
• 70 °C (158 °F) surface temperature
• Cables with concentric copper shield
• Not more than nine cables laid on cable ladder
side by side.
Based on:
• NEC Table 310-16 for copper wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient temperature
• Not more than three current-carrying
conductors in raceway or cable, or earth
(directly buried).
• Copper cables with concentric copper shield
Max
Load
Current
(A)
Cu Cable
(mm
2
)
Max
Load
Current
(A)
Al Cable
(mm
2
)
Max Load
Current
(A)
Cu Wire Size
(AWG/kcmil)
14
3x1.5
61
3x25
22.8
14
20
3x2.5
75
3x35
27.3
12
27
3x4
91
3x50
36.4
10
34
3x6
117
3x70
50.1
8
47
3x10
143
3x95
68.3
6
62
3x16
165
3x120
86.5
4
79
3x25
191
3x150
100
3
98
3x35
218
3x185
118
2
119
3x50
257
3x240
137
1
153
3x70
274
3x (3x50)
155
1/0
186
3x95
285
2x (3x95)
178
2/0
215
3x120
205
3/0