50
ACH550 User’s Manual
Hand Control
This macro configures for drive control using only the control panel with no
automated control. Typically, this is a temporary configuration used prior to control
wiring.
Parameters Changed Relative to HVAC Default
Parameter
Value
Parameter
Value
9902
APPLIC
MACRO
14 (
HAND
CONTROL
)
3415
SIGNAL
3
PARAM
100 (
NOT
SEL
)
1001
EXT
1
COMMANDS
0 (
NOT
SEL
)
3416
SIGNAL
3
MIN
(-)
1002
EXT
2
COMMANDS
0 (
NOT
SEL
)
3417
SIGNAL
3
MAX
(-)
1106
REF
3
SEL
2 (
AI
2)
3418
OUTPUT
3
DSP
FORM
(-)
1201
CONST
SPEED
SEL
0 (
NOT
SEL
)
3419
OUTPUT
3
DSP
UNIT
(-)
1301
MINIMUM
AI
1
0.0%
3420
OUTPUT
3
MIN
(-)
1304
MINIMUM
AI
2
0.0%
3421
OUTPUT
3
MAX
(-)
1401
RELAY
OUTPUT
1
7 (
STARTED
)
4001
GAIN
1.0
1504
MINIMUM
AO
1
0.0mA
4002
INTEGRATION
TIME
60.0 s
1510
MINIMUM
AO
2
0.0mA
4010
SETPOINT
SEL
1 (
AI
1)
1601
RUN
ENABLE
2 (
DI
2)
4101
GAIN
1.0
1608
START
ENABLE
1
0 (
NOT
SEL
)
4102
INTEGRATION
TIME
60.0 s
2108
START
INHIBIT
1 (
ON
)
4110
SETPOINT
SEL
1 (
AI
1)
3207
SUPERV
3
PARAM
0103 (
OUTPUT
FREQ
)
4210
SETPOINT
SEL
1 (
AI
1)
1
SCR
2
AI1
3
AGND
4
10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
10 24V
11 GND
12 DCOM1
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
X1
mA
mA
Not configured
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Not configured
Not configured
Not configured
Not configured
Not configured
Relay output 1 (P 1401)
Default operation:
Ready
=>19 connected to 21
Relay output 2 (P 1402)
Default operation:
Running
=>22 connected to 24
Relay output 3 (P 1403)
Default operation:
Fault (-1)
=>25 connected to 27
Output current:
0(4)…20 mA
Not configured
Analog input circuit common
Not configured
Analog output circuit common
Auxiliary voltage 24 VDC
Common for DI return signals.
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
J1
AI1: 0(2)
…
10 V
AI2: 0(4)
…
20 mA
ON
ON
Jumper Settings