ACH550-UH User’s Manual
55
0131
PID 2 FBK
-
-
-
The
PID
2 controller feedback signal.
• Units and scale defined by PID parameters 4206 & 4207.
0132
PID 1 DEVIATION
-
-
-
The difference between the
PID
1 controller reference value and actual value.
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0133
PID 2 DEVIATION
-
-
-
The difference between the
PID
2 controller reference value and actual value.
• Units and scale defined by PID parameters 4206 & 4207.
0134
COMM RO WORD
0…65535
1
0
Free data location that can be written from serial link.
• Used for relay output control.
• See parameter 1401.
0135
COMM VALUE 1
-32768…+32767
1
0
Free data location that can be written from serial link.
0136
COMM VALUE 2
-32768…+32767
1
0
Free data location that can be written from serial link.
0137
PROCESS VAR 1
-
1
Process variable 1
• Defined by parameters in Group 34: Panel Display / Process Variables.
0138
PROCESS VAR 2
-
1
Process variable 2
• Defined by parameters in Group 34: Panel Display / Process Variables.
0139
PROCESS VAR 3
-
1
Process variable 3
• Defined by parameters in Group 34: Panel Display / Process Variables.
0140
RUN TIME
0…499.99 kh
0.01 kh
0 kh
The drive’s accumulated running time in thousands of hours (kh).
0141
MWH COUNTER
0…9999 MWh
1 MWh
-
The drive’s accumulated power consumption in megawatt hours. Can not be reset.
0142
REVOLUTION CNTR
0…9999
1
0
The motor’s accumulated revolutions in millions of revolutions.
0143
DRIVE ON TIME (HI)
0…65535 days
1 day
0
The drive’s accumulated power on time in days.
0144
DRIVE ON TIME (LO)
0…43200hh:mm:ss
2 s
0
The drive’s accumulated power on time in 2 second ticks (30 ticks = 60 seconds).
0145
MOTOR TEMP
-10...200
°
C/
1
0
0...5000 Ohm /
0…1
Motor temperature in degrees centigrade / PTC resistance in Ohms.
• Applies only if motor temperature sensor is set up. See parameter 3501.
Group 01: Operating Data
Code
Description Range
Resolution
Default
S