74
ACH550-UH User’s Manual
Group 15: Analog Outputs
This group defines the drive’s analog (current signal) outputs. The drive’s analog
outputs can be:
•
Any parameter of the Operating Data group (Group 01).
•
Limited to programmable minimum and maximum values of output current.
•
Scaled (and/or inverted) by defining the minimum and maximum values of the
source parameter (or content). Defining an maximum value (parameter 1503 or
1509) that is less than the content minimum value (parameter 1502 or 1508)
results in an inverted output.
•
Filtered
Group 15: Analog Outputs
Code
Description Range
Resolution
Default
S
1501
AO1 CONTENT SEL
99…199
1
103
Defines the content for analog output AO1.
99 =
EXCITE
PTC
– Provides a current source for sensor type PTC.
Output = 1.6 mA. See Group 35.
100 =
EXCITE
PT
100 – Provides a current source for sensor type
Pt100. Output = 9.1 mA. See Group 35.
101…145 – Output corresponds to a parameter in the Operating
Data group (Group 01).
• Parameter defined by value (value 102 = parameter 0102)
146…199 – Not assigned.
1502
AO1 CONTENT MIN
Depends on selection
-
0.0 Hz
Sets the minimum content value.
• Content is the parameter selected by parameter 1501.
• Minimum value refers to the minimum content value that will be converted to an analog output.
• These parameters (content and current min. and max. settings) provide scale and offset adjustment for the
output. See figure.
1503
AO1 CONTENT MAX
Depends on selection
-
60.0 Hz
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be converted to an analog output.
1504
MINIMUM AO1
0.0…20.0 mA
0.1 mA
4.0 mA
Sets the minimum output current.
1505
MAXIMUM AO1
0.0…20.0 mA
0.1 mA
20.0 mA
Sets the maximum output current.
AO (mA)
AO
CONTENT
P 1504 /
P 1502 / 1508
P 1503 / 1509
AO (mA)
AO
CONTENT
P 1505 /
P 1504 /
P 1503 / 1509
P 1502 / 1508
P 1505 /
P 1511
P 1510
P 1511
P 1510