62
ACH550-UH User’s Manual
10 =
COMM
– Assigns the fieldbus Command Word as the source for the start/stop and direction commands.
• Bits 0,1, 2 of Command Word 1 (parameter 0301) activates the start/stop and direction commands.
• See Fieldbus user’s manual for detailed instructions.
11 =
TIMER
1. – Assigns Start/Stop control to Timer 1 (Timer activated =
START
; Timer de-activated =
STOP
). See
Group 36, Timer Functions.
12…14 =
TIMER
2… 4 – Assigns Start/Stop control to Timer 2…4. See Timer Function 1 above.
1002
EXT2 COMMANDS
0…14
1
1
9
Defines external control location 2 (
EXT
2) – the configuration of start, stop and direction commands.
• See parameter 1001
EXT
1
COMMANDS
above.
1003
DIRECTION 1…3
1
1
9
Defines the control of motor rotation direction.
1 =
FORWARD
– Rotation is fixed in the forward direction.
2 =
REVERSE
– Rotation is fixed in the reverse direction.
3 =
REQUEST
– Rotation direction can be changed on command.
Group 10: AcStart/Stop?Dir
Code
Description Range
Resolution
Default
S