EAS822, EBS852, EBS862
ELECTRONIC UNIT | OI/EAS822/EBS852/EBS862-EN REV. D
11
Delivery status
The individual actuator configuration may vary from the
standard setup above. This information can be displayed via the
user interface.
Unless otherwise specified by the user, the electronic units are
delivered with the following standard configuration:
Conventional communication
Parameter
Setting
Function selection
Positioner, parameter: set point
Set point function
Analog set point
Set point range
4 to 20 mA
Set point characteristic
Linear; set point = position value
Actual value range
4 to 20 mA
Nominal torque / rated force in
±direction
100 %
Automatic speed in ±direction:
100 %
Action in 0 % / 100 %
end position
Keep leak-tight with nominal torque / rated
force
Digital inputs
Digital input 1 Manual / Automatic
switching,
Digital input 2 / 3 Travel command ±
Digital outputs
Digital output 1 ready for operation / error
message,
Digital output 2 / 3 end position signaling
0 % / 100 %
Brake Away Function
Deactivated
Shut-off function
Deactivated
Positioning loop monitoring
Deactivated
Set point monitoring
Deactivated
Alarm Type
Deactivated
Action after restoration of power Switch to Automatic
Working range of actuator
Not set
4
Transport and storage
Inspection
Check the devices immediately after unpacking for possible
damage that may have occurred from improper transport.
Details of any damage that has occurred in transit must be
recorded on the transport documents.
All claims for damages must be submitted to the shipper
without delay and before installation.
Transporting the device
Safety instructions
DANGER
Danger to life due to falling or toppling loads.
Risk of death or serious injury due to the device falling down
or toppling over!
• Standing under suspended loads is prohibited.
• Do not detach the hoisting equipment until installation is
complete.
• Only use the dedicated load pick-up devices (eyebolts) for
suspending the components.
Consider the following items during transport:
• Pay attention to the device weight details.
• Do not expose the device to humidity during transport.
Pack the device accordingly.
• Pay attention to the permissible transportation
temperatures for the device.
Returning devices
For the return of devices, follow the instructions in
Repair
on
page 38.
Storing the device
The electronic units EAS822, EBS852, EBS862 comply with IP
rating IP 20. The electronic units should be stored in accordance
with this IP rating. Condensation is not permitted.
The permissible storage temperatures as well as the ambient
conditions (humidity) should be complied with (see
Device
designs
on page 8).
For longer storage periods, we recommend packing the units in
foil with a dessicant added.
The dessicant must be checked for regularly for effectivity.