Keypad Programming and Basic Operation 6-1
MN448
Chapter 6
Keypad Programming and Basic Operation
The drive is configured and its operation monitored using a remote keypad and display or the PC Tools. Refer to Chapter 5 for
proper electrical connection of the keypad to the drive.
6.1 User Interface
NAVIGATE
Used to display real-time information, to
access and exit parameter edit mode and to
store parameter changes.
UP
Used to increase speed in real-time mode or
to increase parameter values in parameter
edit mode.
DOWN
Used to decrease speed in real-time
mode or to decrease parameter values in
parameter edit mode.
STOP
When drive is in trip mode, this button is
used to reset a tripped drive. In normal
application, when in Keypad mode, this
button is used to stop a running drive.
START
When in keypad mode, the button is used
to start a stopped drive or to reverse the
direction of rotation if bi-directional keypad
mode is enabled (See drive user guide for
more information).
6.2 Real Time Operation
Once the communication has been established between the EC Titanium and REMOTE PANEL, the user can control the EC
Titanium by using the control buttons on the front panel of the REMOTE PANEL.
6.2.1 Pre-setting target speed in keypad mode
Setting parameter
1103
to a value of 1 enables keypad mode with forward direction only, while a value of 2 enables keypad
mode with forward and reverse rotation.
Set parameter
1100
to 1 or 3 to enable the drive to start from the set keypad reference speed.
While the drive is stopped, press the
STOP
key. The value of the digital potentiometer will be displayed, indicating the target
speed. Use the
Up
and
DOWN
keys to select the required target speed.
Press the
STOP
key to return to the real time display showing “
StoP
” or the START key to start the drive ramping up to the
target speed.
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......