A-8 Modbus-RTU Example Connection
MN448
A.9 Additional Information
Register 149: DC Injection Configuration
The parameter value is stored as a combined 16 bit word which is constructed as follows:
High byte
Low byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
DC Injection Mode
DC Injection Duration : 1dp, e.g. 0 – 250 = 0.0 – 25.0s
0 :
DC Injection on Start
1 :
DC Injection on Stop
2 :
DC Injection on Start & Stop
Register 170: Communications Configuration
This Register entry contains multiple data entries, as follows:
High byte
Low byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Trip Configuration
Baud Rate
Drive Address
Data values can be interpreted as follows:
Drive Address
1 to 63
Baud Rate
0
115k2
1
115k2
2
9k6
3
19k2
4
38k4
5
57k6
6
115k2
7
115k2
8
115k2
9
115k2
10
115k2
Trip Time Set-up
0
Comms Loss Trip Disabled
1
30ms Watchdog, Trip on Comms Loss
2
300ms Watchdog, Trip on Comms Loss
3
1000ms Watchdog, Trip on Comms Loss
4
3000ms Watchdog, Trip on Comms Loss
5
30ms Watchdog, Ramp To Stop on Comms Loss
6
300ms Watchdog, Ramp To Stop on Comms Loss
7
1000ms Watchdog, Ramp To Stop on Comms Loss
8
3000ms Watchdog, Ramp To Stop on Comms Loss
Summary of Contents for EC Titanium ECS100A1H1DF4
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......