Parameter Definitions 10-3
MN448
Parameters in the Short parameter mode
No.
Name/Value
e
Description
Default
20 LIMITS
Maximum frequency
2008
MAXIMUM FREQUENCY /
SPEED LIMIT
Maximum output frequency or motor speed limit – Hz or rpm.
If parameter
9908
MOTOR RATED SPEED > 0, the value entered /
displayed is in RPM
133 Hz
2007
…133.0 Hz
Maximum frequency
21 STOPPING MODE /
POWER LOSS RESPONSE
Stop mode of the motor
2102
STOP MODE
Selects the motor stop function
Setting
On Disable
On Mains loss
0
Ramp to Stop
Ride Through
(Recover energy from load to
maintain operation)
1
Coast
Coast
2
Ramp to Stop
Fast Ramp to Stop
3
Ramp to Stop
with AC flux braking
Fast Ramp to Stop
Note:
Ramp to Stop will follow 2203 DECEL RAMP TIME Fast Ramp to
Stop uses 2206 2nd DECEL RAMP TIME or will coast to a stop
if 2206 = 0
0
22 ACCEL/DECEL
Acceleration and deceleration times
2202
ACCELERATION
RAMP TIME
Acceleration ramp time from 0 to base speed (Parameter
9907
MOTOR
RATED FREQUENCY) in seconds.
30.0 s
0.00…600.0 s
Time
2203
DECELERATION
RAMP TIME
Deceleration ramp time from base speed (Parameter
9907
MOTOR
RATED FREQUENCY) to standstill in seconds.
When set to zero,
fastest possible ramp time without trip is activated.
30.0 s
0.00…600.0 s
Time
Summary of Contents for EC Titanium Series
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......