10-6 Parameter Definitions
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
11
REFERENCE SELECT
The drive can accept a variety of references in addition to the
conventional analog input, potentiometer and keypad signals.
1100
KEYPAD MODE RESTART
FUNCTION
This parameter is active only when operating in Keypad Control Mode
(parameter 1103 PRIMARY COMMAND SOURCE MODE = 1 or 2).
3
0: MINIMUM SPEED,
KEYPAD START
Keypad Start and Stop keys are active, and control terminals 1 and 2 must
be linked together. The drive will always start at the Minimum Frequency /
Speed (parameter 2007 )
1:
PREVIOUS SPEED,
KEYPAD START
Keypad Start and Stop keys are active, and control terminals 1 and 2 must
be linked together.
2:
MINIMUM SPEED,
TERMINAL ENABLE
Allows the drive to be started from the control terminals directly, and the
keypad Start and Stop keys are ignored.
The drive will always start at the Minimum Frequency / Speed (parameter
2007)
3:
PREVIOUS SPEED,
TERMINAL ENABLE
Allows the drive to be started from the control terminals directly, and the
keypad Start and Stop keys are ignored. The drive will always start at the
last operating Frequency / Speed.
4:
CURRENT SPEED ,
KEYPAD START
Keypad Start and Stop keys are active and control terminals 1 and 2 must
be linked together. The drive will always start at the current Frequency /
Speed.
5:
PRESET SPEED 4 ,
KEYPAD START
Keypad Start and Stop keys are active and control terminals 1 and 2 must
be linked together. The drive will always start at the Frequency / Speed set
in Preset Speed 4 (parameter 1205).
6:
CURRENT SPEED ,
TERMINAL START
Control terminals 1 and 2 must be linked together. The drive will always
start at the current Frequency / Speed.
7:
PRESET SPEED 4 ,
TERMINAL START
Control terminals 1 and 2 must be linked together. The drive will always
start at the Frequency / Speed set in Preset Speed 4 (parameter 1205).
1103
PRIMARY COMMAND
SOURCE MODE
0
0:
TERMINAL
CONTROL.
The drive responds directly to signals applied to the control terminals.
1:
UNI-DIRECTIONAL
KEYPAD CONTROL
The drive can be controlled in the forward direction only using an external
or remote Keypad
2:
BI-DIRECTIONAL
KEYPAD CONTROL.
The drive can be controlled in the forward and reverse directions using an
external or remote Keypad. Pressing the keypad START button toggles
between forward and reverse.
3:
MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) using the internal accel / decel ramp
4:
MODBUS NETWORK
CONTROL.
Control via Modbus RTU (RS485) interface with accel / decel ramps
updated via Modbus
5:
PI CONTROL
User PI control with external feedback signal
6:
PI ANALOG
SUMMATION CONTROL.
PI control with external feedback signal and summation with analog input 1
7:
CANopen
Control with internal acceleration / deceleration ramps
8:
CANopen
Control with acceleration / deceleration ramps
Summary of Contents for EC Titanium Series
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......