10-8 Parameter Definitions
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
1302
ANALOG IN 1 SCALING
Scales the analog input by this factor, (as a % of the full scale range of this
input).
100.0
0.0…2000.0 %
Example: If parameter
1300
ANALOG INPUT 1 FORMAT is set for 0 – 10V,
and the scaling factor is set to 200.0%, a 5 Volt input will result in the drive
running at maximum speed as set in parameter
2008
MAX SPEED LIMIT
1304
ANALOG IN 2 FORMAT
Selects the type of reference source into terminal 4.
U 0-0
U 0-0
0 to 10 Volt Signal
A 0-0
0 to 20mA Signal
t 4-0
4 to 20mA Signal, the DRIVE will trip and show the fault code
000
if the
signal level falls below 3mA
r 4-0
4 to 20mA Signal, the DRIVE will ramp to stop if the signal level falls below
3mA
t 0-4
20 to 4mA Signal, the DRIVE will trip and show the fault code
000
if the
signal level falls below 3mA
r 0-4
20 to 4mA Signal, the DRIVE will ramp to stop if the signal level falls below
3mA
Ptc-th
Use for motor thermistor
Summary of Contents for EC Titanium Series
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......