Parameter Definitions 10-11
MN448
Parameters in the Long parameter mode
No.
Name/Value
Description
Default
21
START/STOP
Start and Stop modes of the motor
2101
FLYING START
Starting the drive connected to a rotating motor.
Size 2 drives only, DC injection time on start for Size 1 drives
2
0:
DISABLED
1:
ENABLED
When enabled, on start up the drive will attempt to determine if the motor is
already rotating, and will begin to control the motor from its current speed.
A short delay may be observed when starting motors which are not turning/
On Size E1 only this parameter Sets a time for which DC current is injected
into the motor to ensure it is stopped when the drive is enabled.
2:
ENABLED ON TRIP,
BROWN OUT OR
COAST STOP
Spin start is only activated following the events listed, otherwise it is
disabled
2102
STOP MODE
Selects the motor stop function
Setting
On Disable
On Mains loss
0
Ramp to Stop (
2203
DECEL
RAMP TIME)
Ride Through (Recover energy
from load to maintain operation)
1
Coast
Coast
2
Ramp to Stop (
2203
DECEL
RAMP TIME)
Fast Ramp to Stop (
2206
2nd
DECEL RAMP TIME), coast if
2206
is zero.
3
Ramp to Stop (
2203
DECEL
RAMP TIME) with AC flux
braking
Fast Ramp to Stop (
2206
2nd
DECEL RAMP TIME), coast if
2206
is zero.
0
2104
DC INJECTION TIME ON
STOP
Defines the time for which a DC current is injected into the motor once the
output frequency reaches 0.0Hz. The voltage level is the same as the boost
level set in parameter
2603
.
Duration
Index 1
0.0
0.0…25.0 s
Defines the time for which DC current is injected into the motor. The voltage
level is the same as the boost level set in parameter
2603
.
DC INJECTION MODE
Index 2
0
0
DC injection on STOP at the voltage level set in
2603
after the output
frequency has reached 0.0Hz and for the time set in Index 1. This can be
useful to ensure the motor has reached a complete stop before the drive
disables.
1
DC injection on START at the voltage level set in
2603
and for the time
set in Index 1 immediately after the drive is enabled, prior to the output
frequency ramping up from zero. This can be used to ensure the motor is at
a standstill prior to starting.
2
DC injection on STOP and START (at both of the settings 0 and 1 above).
2108
TERMINAL MODE
RESTART FUNCTION
Defines the behavior of the drive relating to the enable digital input and also
configures the Automatic Restart function.
Auto-0
Edge-r
Following Power on or reset, the drive will not start if Digital Input 1 remains
closed. The Input must be closed after a power on or reset to start the
drive.
Auto-0
Following a Power On or Reset, the drive will automatically start if Digital
Input 1 is closed.
Auto- to Auto-5
Following a trip, the drive will make up to 5 attempts to restart at 20 second
intervals. The drive must be powered down to reset the counter. The
numbers of restart attempts are counted, and if the drive fails to start on
the final attempt, the drive will fault and will require the user to manually
reset the fault.
Summary of Contents for EC Titanium Series
Page 1: ... MN448_May 2020 May 2020 EC Titanium Manual User s guide ...
Page 10: ...1 4 Introduction MN448 ...
Page 20: ...3 4 Mechanical Information and Mounting MN448 ...
Page 26: ...4 6 Electrical Installation and Planning MN448 ...
Page 32: ...5 6 Control Pad Wiring and Keypad Interface MN448 ...
Page 36: ...6 4 Keypad Programming and Basic Operation MN448 ...
Page 44: ...8 4 Parameter Navigation and Groups MN448 ...
Page 51: ...9 7 Control Modes MN448 ...
Page 77: ...11 8 Standalone Motor and ABB Drive Setup MN448 ...
Page 99: ...A 12 Modbus RTU Example Connection MN448 ...
Page 102: ......