3.6 Setting the Configuration
Chapter 3: Configuration
142
493-0736-11 (6-2)
When tuning is first performed, or after the Autotuner has been reset, not only the
set selected by
GainSchedulingSignal
(here 0.0–Limit1) is filled but also the rest
of the table.
Table 103
Gain Scheduling First Tuning.
When tuning the second time (and the next set is selected) the first set is left
untouched but the one selected (here Limit2–100.0) is filled along with the rest of
the table.
Table 104
Gain Scheduling Second Tuning.
When tuning the third time (and the remaining set is pointed out) the only set
affected is the one pointed out (here Limit1–Limit2).
Table 105
Gain Scheduling Third Tuning.
After this, for every tuning performed only the set pointed out is filled.
Note:
If you reset the Gain Scheduler, the Autotuner fills in the whole table as
described in Table 103, not just the selected parameter set.
GainSchedulingSignal
K
TI
TD
Limit2–100.0
Tuning 1
Tuning 1
Tuning 1
Limit1–Limit2
Tuning 1
Tuning 1
Tuning 1
0.0–Limit1
Tuning 1
Tuning 1
Tuning 1
GainSchedulingSignal
K
TI
TD
Limit2–100.0
Tuning 2
Tuning 2
Tuning 2
Limit1–Limit2
Tuning 2
Tuning 2
Tuning 2
0.0–Limit1
Tuning 1
Tuning 1
Tuning 1
GainSchedulingSignal
K
TI
TD
Limit2–100.0
Tuning 2
Tuning 2
Tuning 2
Limit1–Limit2
Tuning 3
Tuning 3
Tuning 3
0.0–Limit1
Tuning 1
Tuning 1
Tuning 1
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......