3.6 Setting the Configuration
Chapter 3: Configuration
158
493-0736-11 (6-2)
When
ManualBehavior
is set to TrueManual and the
ManualEnable
input has the
value True, the Hand key is disabled. If the
ManualEnable
input is False, the
Hand key is enabled and can toggle the Control Mode.
The transition from
Auto
to
Manual
can be made by either the Hand key or the
ManualEnable
input. However, the transition from
Manual
to
Auto
can be made
only by the Hand key.
Figure 55
ManualBehavior = TrueManual.
DDC
The DDC function has two digital inputs,
DDCIncrease
and
DDCDecrease
, and
one parameter
DDCTime
. The
DDCIncrease
and
DDCDecrease
inputs only
control the
ControlSignal
when the ControlMode is Manual.
Activating
DDCIncrease
makes the
ControlSignal
increase; activating
DDCDecrease
makes the
ControlSignal
decrease. The rate at which the
ControlSignal
changes when one of these inputs is activated is defined by the
parameter
DDCTime
.
Activating both
DDCIncrease
and
DDCDecrease
has the same effect as having
both inputs deactivated.
ManualEnable Input
Hand key
ManualStatus Output
Not
pressed
True
False
Pressed
Manual
Available in
ECA06
ECA60
ECA600 EMA60
-
X
X
-
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......