Chapter 3: Configuration
3.6 Setting the Configuration
493-0736-11 (6-2)
191
Connection to the analog source is made via the input
Signalx
(where x = 1, 2 or
3). If
Signalx
is off then the corresponding bar graph is turned off. The text “Off”
is shown on the display instead of a numerical value when the signal is accessed
from the Operator option List.
Table 145
EMA60
Operator Block Inputs.
Display
By pressing the next key on the front panel the value of
Signal1
,
Signal2
or
Signal3
can be presented on the display, scaled in the selected engineering units
(EGU). The value of the
Signal
input is always truncated internally in the range
0.0% to 100.0%. The scaling into EGU is made using the truncated range.
The EGU scaling is determined by the parameters
MinValue
and
MaxValue
. Five
significant digits are available.
For example:
• Setting the
NumberOfDecimals
parameter to two (2) makes
MinValue
and
MaxValue
range from –999.99 to 999.99.
• Setting the
NumberOfDecimals
parameter to four (4) makes
MinValue
and
MaxValue
range from –9.9999 to 9.9999.
Note:
If the value to be displayed exceeds five digits at any time, the rightmost
digit is dropped.
The parameter
Unit
adds a unit label on the display.
Tag
is a text string displayed on the top line of the display in Operator Mode when
the section is selected for display.
Tag
can hold twenty (20) characters, but the top
line cannot display all of them. If the length of
Tag
is less than or equal to 16, the
full length is displayed. If the length of
Tag
is greater than 16, then 15 characters
are displayed followed by the character “…”.
Inputs
Name
Connection
Signal1
Off, Analog
Signal2
Off, Analog
Signal3
Off, Analog
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......