Chapter 5: Technical Data
5.6 Output Signals
493-0736-11 (6-2)
205
• Inactive = 0 to 5 V, active = 16 to 30 V
5.6
Output Signals
AO1, AO2, AO3
• Three analog outputs, 0–20 mA or 4–20 mA. Loading 0 to 650
Ω
.
• Load dependence < 0.2 % for a change from 0 to 60
Ω
.
DO1, DO2, DO3, DO4, DO5, DO6
• Six digital outputs, 24 V 250 mA.
5.7
Computer Communication
• RS485 serial interface, COMLI or MODBUS RTU protocol.
• RS232 serial interface, COMLI or MODBUS RTU protocol.
5.8
Safety Functions
Supply Failure
• Restart from present position (3-state pulse output) or a preset position.
Input/Output Signal Failure
• Failure of the analog input/output signal initiates an alarm.
5.9
Indications
Process and Set Point Values
• Analog bar graph display with 3.33 % resolution.
• Calibrated 0 to 100 %.
• Display normally shows Process Value. Automatically reverts to showing the
Process Value 5 seconds after the user has finished examining other values.
Output Signal
• Analog bar graph display with 5 % resolution.
• Calibrated 0 to 100 %.
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......