Appendix A: Application Examples
A.2 Temperature Control and Communication with COMLI
493-0736-11 (6-2)
223
Configuration
Preset Configuration
Select the Default Setup from the Preset Configurations.
1
System
→
Miscellaneous
→
Setup
=
Default.
Inputs
The TT1 output signal range is 0–5V (for 0–400ºC) and the FT1 output signal
range is 0–20 mA:
1
Inputs
→
Analogue Inputs
→
AI1
→
Mode
=
0–5V.
2
Inputs
→
Analogue Inputs
→
AI1
→
Identity
=
Temp.
3
Inputs
→
Analogue Inputs
→
AI2
→
Mode
=
0–20mA.
4
Inputs
→
Analogue Inputs
→
AI2
→
Identity
=
Flow.
Miscellaneous
SetUp
Default
Cancel
OK
AI1: Ana In 1
Mode
0–5V
Cancel
OK
AI1: Ana In 1
Identity
Temp
Cancel
OK
AI2: Ana In 2
Mode
0–20 mA
Cancel
OK