Appendix A: Application Examples
A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2)
231
4
Inputs
→
Analog Inputs
→
AI2
→
Identity
=
Pressure.
Filtering
Set the time constant for AI2 to 2seconds:
1
Inputs
→
Analog Inputs
→
AI2
→
FilterTime
=
2 seconds.
Process Value
The pressure signal is to be used as the Process Value and is in the range –1.0 to
+1.0kPa:
1
Operator
→
(PID1 – ECA600 only
→
) Process Value
→
NumberOfDecimals
=
1.
2
Operator
→
(PID1 – ECA600 only
→
) Process Value
→
PVMinValue
=
–1.
AI2: Ana In 2
Mode
4–20mA
Cancel
OK
AI2: Ana In 2
Identity
Pressure
Cancel
OK
AI2: Pressure
FilterTime
2
Cancel
OK
Process Value
NumberOfDecimals
1
Cancel
OK