Appendix A: Application Examples
A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2)
235
Outputs
The feed to the potentiometer should be set to 5.0mA which gives 0–5V output
since the potentiometer resistance is 1000
Ω
:
1
Outputs
→
Analog Outputs
→
AO1
→
Mode
=
Direct.
2
Outputs
→
Analog Outputs
→
AO1
→
FixedCurrent = 5 mA.
3
Outputs
→
Analog Outputs
→
AO1
→
Identity
=
PotFeed.
Configure DO1 and DO2 to the low and high pressure alarms:
1
Outputs
→
Digital Outputs
→
DO1
→
Mode
=
PositiveLogic.
ThreeStatePulse
Feedback
AI1[Value]
Cancel
OK
AO1: Ana Out 1
Mode
Direct
Cancel
OK
AO1: Ana Out 1
Fixed Current
5mA
Cancel
OK
AO1: Ana Out 1
Identity
PotFeed
Cancel
OK