3.6 Setting the Configuration
Chapter 3: Configuration
62
493-0736-11 (6-2)
• Any digital input of any block type can be connected to any digital output of
any block type.
Overview
The controllers each have six main configurable sections, called columns:
• The Input column contains blocks that accept signals from direct wiring, or
from the communication channels, or from values input by the user on the front
panel. These inputs may be analog or digital.
• The Input Functions column contains blocks that mainly manipulate the input
signals from the Input Blocks. There are three types – Arithmetic Function
Blocks (FA), Logic Function Blocks (FL) and Other Function Blocks (FO).
The Other Function Blocks have inputs and outputs that are both analog and
digital.
• The Set Point column contains Set Points.
• The Alarm column contains Absolute alarms and Deviation alarms.
• The Control column contains Control and Output Configuration blocks which
carry out control and related functions.
• The Output column contains Output blocks that pass the analog or digital
control signals either to the communications channels or to directly wired
outputs.
• The Operator Block processes all user interaction and scales the Process Value
into engineering units.
• The System column contains communication configurations, status and
language.
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......