3.6 Setting the Configuration
Chapter 3: Configuration
66
493-0736-11 (6-2)
Terminal Input = Differential Pressure
and
Block Output = Flow
The filter function of the analog Input block is activated by setting the parameter
Filter Time
to a non-zero value. The filter characteristic is shown below.
Figure 37
Filter Characteristic.
Notes:
• For details of the parameter
Alarm
please refer to Appendix B Error, Warning
and Information Messages.
• If a warning is set the controller displays a message while continuing to operate
normally.
• The parameter
Loop
is used only on the ECA600. Alarms can be set to act on
either loop independently. The control block designated by the
Loop
parameter
for alarm will react according to the parameter
ErrorBehavior
in the Control
block. The other Control block (loop) will continue to function as normal.
Differential Pressure
Flow
∼
Block Output = e
-t/FilterTime
time (FilterTime = 20 seconds)
V
alue Output
100
90
80
70
60
50
40
30
20
10
0
0 10
20
30
40
50
60
70
80
90
100
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......