3.6 Setting the Configuration
Chapter 3: Configuration
194
493-0736-11 (6-2)
Table 148
System Status Outputs.
COM Setup
There are five parameters associated with communications:
•
ComProtocol
which may be set to COMLI or MODBUS RTU.
•
Identity
which may be set to any number within the range 1 to 247
•
RS-485BaudRate
which may be set to a maximum value of 38,400 baud.
•
RS-232BaudRate
which may be set to a maximum value of 38,400 baud
•
WriteEnable
which may be set to On or Off.
Communication modes can be switched both from the front and via the
ComputerModeEnable
input (described above). The Front Switch (via the
Operator Option List) and
ComputerModeEnable
have equal priorities.
If
WriteEnable
is set to Off, a supervisory system can not write to the controller´s
registers when the Communication Mode is Local.
Table 149
WriteEnable is Off.
Note.
See Appendix E for a full list of communication I/O bits and registers
Outputs
Name
Type
Computer Mode
False = Local, True = Computer
ErrOr Warn
Refer to Appendix B for more information
Communication
Mode
Write Operations
Operator Front Panel
Access
Local
Impossible
Unrestricted
Computer
Possible
Restricted
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......