Appendix A: Communication
A.5 Communication Area Mapping
493-0736-11 (6-2)
291
Note 2.
For ‘Controller Action’, the value 0 (zero) denotes Reversed, and the
value 1 (one) denotes Direct. The value 0 (zero) is also used for Unknown (Read
only).
Note 3
. A supervisory system, e.g. SattGraph 5000, can conveniently increase or
decrease the output value of the ECA controller by use of two bits in the variable
Control 00D0
16
. The analog output signal value (loop 1) will increase as long as
bit 1 is active (bit 1 = 1 and bit 3 = 0) and will decrease if bit 3 is active (bit 3 = 1
and bit 1 = 0). The speed of increase/decrease depends on the controller sample
time.
Figure 3
External increase/decrease of the analog output signal using two bits in the variable
Control
00D016.
Register Map
Each register consists of a 16-bit integer containing a value between 0 and 65535.
Variable
Access
Register
AIC1
Read/Write R1
AIC2
Read/Write R2
AIC3
Read/Write R3
AIC4
Read/Write R4
AIC5
Read/Write R5
AIC6
Read/Write R6
AIC7
Read/Write R7
AIC8
Read/Write R8
AIC9
Read/Write R9
AIC10
Read/Write R10
AIC11
Read/Write R11
AIC12
Read/Write R12
Output signal
(Loop 1)
Bit 1 = 1
Bit 3 = 0
Bit 1 = 0
Bit 3 = 0
Bit 1 = 0
Bit 3 = 1
Summary of Contents for ECA06
Page 1: ...Version 1 05 ECA06 60 600 EMA60 Configuration and Installation ...
Page 2: ......
Page 3: ...ECA06 60 600 EMA60 Configuration and Installation ...
Page 10: ...Contents vi 493 0736 11 6 2 ...
Page 16: ...1 5 Version information Chapter 1 Introduction 16 493 0736 11 6 2 ...
Page 200: ...4 2 Annual Check Chapter 4 Maintenance 200 493 0736 11 6 2 ...
Page 286: ...Appendix A Configuration Work Sheets 282 493 0736 11 6 2 ...
Page 304: ...B 1 Total Reset Appendix B Special Modes 298 493 0736 11 6 2 ...
Page 308: ...Index 302 493 0736 11 6 2 ...
Page 309: ......