background image

GB

Operation

• Switch off: touch the operating element: The last adjusted

brightness value will be stored and the lighting
facility will be switched off.

b. Parallel mode (Fig. 2) (Extension)

• Actuate operating element of the extension: All memory

touch controllers STD-MTS are switched or dimmed
simultaneously via the extension. Lighting facilities can
also be operated with a uniform brightness value.

• Hold down the operating element of the extension for

about 10 seconds.
- The lighting facilities are set to the maximum brightness
value and can be operated "synchronously" then.

Summary of Contents for EG 7460

Page 1: ...D ABB Memory Taststeuergerät STD MTS EG 7460 Betriebsanleitung Nur für autorisiertes Elektrofachpersonal 0173 1 5932 26979 GB NL F D I ...

Page 2: ...D Fig 1 N L1 x EVG EEC EVSA N L 1 N STD MTS EG 7460 D F GB NL I ...

Page 3: ...D Fig 2 N L1 x EVG EEC EVSA N L 1 N EVG EEC EVSA L N x N 1 STD MTS EG 7460 STD MTS EG 7460 D F GB NL I ...

Page 4: ...nung 230 V 10 50 Hz Nennstrom 4 A cos ϕ 0 9 oder 3 A cos ϕ 0 5 Schaltleistung 700 VA Leistungsaufnahme 1 W Nebenstelleneingang 230 V 10 50 Hz Steuerspannung 1 V 10 V Steuerstrom max 50 mA DC Umgebungs temperaturbereich 0 bis 35 C ...

Page 5: ...pen Die maximale Anzahl der anzuschließenden EVG ergibt sich aus den Kenndaten der jeweiligen Hersteller Die Re laisbelastung darf 4 A max 10 EVG nicht überschreiten EinintegrierterEinschaltstrombegrenzerverhindertdiesonst hohenEinschaltstömederEVG SollengrößereLeistungen gesteuert werden ist ein externes Schütz vorzusehen ACHTUNG Stellen Sie sicher dass bei Arbeiten an dem Memory taststeuergerät ...

Page 6: ...n Die Einbauversion des Memorytaststeuergerätes für Ver teilungen wird auf eine Normschiene 35 mm aufgerastet ACHTUNG Der Steuerausgang 1 V 10 V vom Memorytast steuergerät STD MTS ist keine Sicherheitsklein spannung Hinweise zur Montage ...

Page 7: ...nnung darf jedoch 100 V nicht überschreiten das entspricht in der Praxis minde stens 100 m Leitungslänge Die Anzahl der Taster ist auf 100 m Leitungslänge unbe grenzt Bei Verwendung von beleuchtbaren Tastern sind diese nur mit N einsetzbar Kontaktparallele Beleuchtung ist nicht zulässig Ungewollte Schaltvorgänge werden vermieden wenn Sie Steuer und Lastleitung nicht in einem Kabel führen ACHTUNG D...

Page 8: ...wechselt wenn er automa tisch auf einen minimalen Helligkeitswert springt Leuchten auf den gewünschten Helligkeitswert einstel len und Taste loslassen Ca 30 Sekunden nach dem Loslassen springt das Memorytaststeuergerät STD MTS automatisch wieder auf Maximum Das ist das Zeichen für die ordnungsge mäße Durchführung der Einstellarbeiten Falls dieser Fall nicht eintritt die Einstellung der Grund helli...

Page 9: ...rät STD MTS die sen Wert und schaltet bei der nächsten Bedienung mit Maximalhelligkeit ein keine Memory Funktion mehr Das Memorytaststeuergerät STD MTS steuert bei erster BedienungvonHellnachDunkel wobeimitjedemStopdie Dimmrichtung umgekehrt wird Bei maximaler Helligkeit stoppt der Dimmer bei minimaler ändert sich die Dimm richtung Wird durch Dimmen Heller eingeschaltet so ist die Dimmrichtung von...

Page 10: ...alten VommomentanenHelligkeitswertanwird heller gestellt bis der maximale Hellig keitswert erreicht ist Maximumstop Dunkler Bedienelement gedrückt halten VommomentanenHelligkeitswertanwird dunkler gestellt bis der minimale Hellig keitswert dunkel erreicht ist Hält man dasBedienelementweitergedrückt wird wiederhellergestellt bisMaximumstop Ausschalten Bedienelement kurz antippen Der zuletzt eingest...

Page 11: ...n über die Neben stelle zeitgleich geschaltet bzw gedimmt Beleuch tungsanlagen lassen sich auch mit einheitlichem Hellig keitswert betreiben Bedienelement der Nebenstelle ca 10 Sekunden ge drückt halten Die Beleuchtungsanlagen werden auf maximalen Helligkeitswert gestellt und lassen sich dann synchron betreiben Bedienung ...

Page 12: ...annung AUS EIN schalten Mindesthelligkeit zu hoch ein gestellt neu einstellen Licht brennt nicht Steuerspannung 1 10 V kurzgeschlossen Netzspannung AUS EIN schalten Minsdesthelligkeit zu niedrig eingestellt neu einstellen Vorgeschaltete Sicherung erneuern defekte Leuchtstofflampe auswechseln EVG austauschen defektes Steuergerät wechseln ...

Page 13: ...50 Hz Courant nominal 4 A cos ϕ 0 9 ou 3 A cos ϕ 0 5 Puissance de rupture 700 VA Puissance absorbée 1 W Entrée de poste supplémentaire 230 V C A 10 50 Hz Tension de commande 1 V 10 V Courant de commande max 50 mA DC Zone de température ambiante 0 à 35 C ...

Page 14: ...esballastsélectriques à raccorder résulte des données caractéristiques des fabricantsrespectifs Lachargederelaisnedoitpasdépasser 4 A maximum env 10 ballasts Un limiteur de courant de démarrage intégré empêche les courants de démarrage ordinairement élevés des ballasts électriques Au cas où des puissances plus élevées doivent être commandées une protection externe doit être prévue ATTENTION Assure...

Page 15: ...gedecontrôleuràeffleurementmemory STD MTS pour des distributions est fixée sur une barre normalisée de 35 mm ATTENTION La sortie de commande 1 V 10 V de le contrôleur à effleurement memory STD MTS n est pas une ten sion de sécurité minimum Remarques concernant le montage ...

Page 16: ...fois pas dépasser 100 V cela correspond en pratique à une longueur de ligne d au moins 100 m Le nombre de boutons poussoirs est illimité sur une longueur de ligne de 100 m Lors de l utilisation de boutons poussoirs pouvant être éclairés ceux ci doivent être raccordés au neutre Un éclairage sur contacts parallèles n est pas autorisé Des opérations de couplage non voulues peuvent être évitées si vou...

Page 17: ...e de programmation lorsqu elle se met automatiquement sur une valeur de luminosité minimale Régler la valeur de luminosité désirée des lampes et lâcher la touche Environ 30 secondes après avoir lâché la touche le contrôleur à effleurement memory STD MTS se remet automatiquement sur la valeur maximum C est signe que les travaux de réglage ont été réalisés dans les règles de l art Si ce n est pas le...

Page 18: ...dcettevaleurets enclenche àlaprochaine commandeaveclaluminositémaximum plusdefonction mémoire Lors de la première commande le contrôleur à effleu rement memory STD MTS règle l intensité lumineuse de clair à foncé le sens de variation étant inversé à chaque arrêt Dans le cas d une luminosité maximum le variateur s arrête en cas d une luminosité minimum le sens de variation se modifie Le sens de var...

Page 19: ...aintenirledoigtsurl élémentdecommande A partir de la valeur de luminosité momen tanée la lumière devient plus claire jusqu à ce que la valeur de luminosité maximum soit atteinte stop maximum Plus foncé Maintenir le doigt sur l élément de com mande A partir de la valeur de luminosité momentanée la lumière devient plus fon cée jusqu à ce que la valeur de luminosité minimum soit atteinte Si on contin...

Page 20: ...postesupplémen taire Toutes les contrôleurs à effleurement memory STD MTS sont réglées en même temps par l inter médiaire du poste supplémentaire Des installations d éclairage peuvent être actionnées aussi avec une seule valeur de luminosité Maintenirledoigtpendant10secondesenvironsurl élé mentdecommandedupostesupplémentaire Lesinstal lationsd éclairagesontrégléessurlavaleurdeluminosité maximum et...

Page 21: ... de réseau MARCHE ARRET Luminosité minimum réglée trop haut procéder à un nouveau réglage La lumière ne brûle Tension de commande 1 V pas 10 V court circuitée Commuter la tension de réseau MARCHE ARRET Luminosité minimum réglée tropbas procéderàunnouveau réglage Remplacer le fusible placé en amont Remplacer le tube fluorescent défectueux Remplacer les ballasts ...

Page 22: ...ge 230 V 10 50 Hz Nominal current 4 A cos ϕ 0 9 or 3 A cos ϕ 0 5 Switching capacity 700 VA Power consumption 1 W Extension input 230 V 10 50 Hz Control voltage 1 V 10 V Control current max 50 mA DC Ambient temperature range 0 to 35 C ...

Page 23: ...mum number of connectable ballasts is specified in the rating of the corresponding manufacturer Relay load must not exceed a maximum of 4 A 10 ballasts An integrated surge limiter avoids the otherwise high ma king currents of the ballasts If higher capacities are to be controlled an external contactor has to be provided ATTENTION When working at the memory touch controller STD MTS make sure that t...

Page 24: ...version of the memory touch controller for distribution lines is latched onto a standard 35 mm busbar ATTENTION The control input 1 V 10 V of the memory touch controller STD MTS is not safety extra low voltage Instructions referrring to installation ...

Page 25: ...ust not exceed 100 V in practice this corresponds to a line length of at least 100 m The number of pushbuttons over a line length of 100 is unlimited If lightable pushbuttons are used they have to be applied only via their N connection A contact parallel lighting is not permitted Undesired switching operations will be avoided when the control and the load line are not conducted in the same cable A...

Page 26: ...tched to programming mode when it jumps automatically to a minimum brightness value Adjust lamps to the desired brightness value and release key About 30 seconds after releasing the memory touch controller STD MTS jumps back onto maximum again This is the sign that the adjustment works have been properly completed If this does not occur please try to adjust the basic brightness again ...

Page 27: ...oses this value When it is actuated next time it will switch on at maximum brightness loss of memory function Upon its first actuation the memory touch controller STD MTSgoesfromlighttodarkandviceversa whereby the dimming direction is reversed at each stop At maximum brightness the dimmer stops at minimum brightness the dimming direction changes If Brighter is set by dimming the dimming direction ...

Page 28: ...ld the operating element down Starting with the current brightness value the device will be set to brighter until the max brightness value has been reached maximum stop Darker hold the operating element down Starting with the current brightness value the device will be set to darker until the min brightness value dark has been reached If you continue holding down the operating element beyond this ...

Page 29: ...ctuate operating element of the extension All memory touch controllers STD MTS are switched or dimmed simultaneously via the extension Lighting facilities can also be operated with a uniform brightness value Hold down the operating element of the extension for about 10 seconds Thelightingfacilitiesaresettothemaximumbrightness value and can be operated synchronously then ...

Page 30: ...ed switch ON OFF mains voltage minimum brightness is set too high readjust it Light does not burn control voltage 1 10 V short circuited switch ON OFF mains voltage minimum brightness set too low readjust it replace series connected fuse replace defective fluorescent lamp replace ballast replace defective control device ...

Page 31: ...spanning 230 V 10 50 Hz Nominale stroom 4 A cos ϕ 0 9 of 3 A cos ϕ 0 5 Schakelvermogen 700 VA Opgenomen vermogen 1 W Nevenpostingang 230 V 10 50 Hz Stuurspanning 1 V 10 V Stuurstroom max 50 mA Radio en Omgevingstemperatuur 0 tot 35 C ...

Page 32: ...n te regelen Het maximale aantal aan te sluiten EVSA s kan worden bepaald aan de hand van de gegevens van de fabrikant van de EVSA Het relais mag niet zwaarder worden belast dan 4 A ca 10 EVSA s Een geïntegreerde inschakelstroombegrenzer voorkomt inschakelstroompieken van de EVSA s Moeten er grotere vermogensgestuurdworden dandienteenexternrelaiste worden aangebracht LET OP Zorg ervoor dat bij wer...

Page 33: ...van het memory tipstuurapparaat is geschikt voor montage op 35 mm normrail LET OP De stuuruitgang 1 V 10 V van het memory tip stuurapparaat STD MTS is geen veiligheidslaagspan ning Installation using an extension input parallel mode Aanwijzingen voor de montage ...

Page 34: ...niet groter zijn dan 100 V hetgeen in de praktijk overeenkomt met een leiding van minimaal 100 m Het aantal impulsdrukkers kent bij een leiding van 100 m geen beperkingen Bij gebruik van verlichte impulsdrukkers kunnen deze uitsluitend met N gebruikt worden Contactparallelle verlichting is niet toegestaan Ongewenst schakelen wordt voorkomen door de stuur en lastleiding niet samen in één kabel of b...

Page 35: ...apparaat STD MTS is actief zodra het apparaat automa tisch naar de minimale helderheid springt Stel de verlichting op de gewenste helderheid in en laat de toets los Ca 30 seconden na het loslaten springt het memory tipstuurapparaat STD MTS automatisch weer naar het maximum Dit betekent dat de basishelderheid correct werd ingesteld Is dit niet het geval stel dan de basishelderheid opnieuw in ...

Page 36: ...emory tipstuurapparaat STD MTS deze helder heidswaarde en schakelt bij het volgend gebruik met de maximale helderheid in geen memoryfunctie meer Het memory tipstuurapparaat STD MTS stuurt bij het e erste bediening van licht naar donker waarbij bij elke stop de dimrichting wordt omgekeerd Bij maximale helderheid stopt de dimmer bij minimale helderheid wordt de dim richting omgekeerd Wordt d m v dim...

Page 37: ...den Vanaf de actuele helderheidswaarde wordt de helderheid vergroot totdat het maximaleniveaubereiktis maximumstop Donkerder Bedienelement ingedrukt houden Vanaf de actuele helderheidswaarde wordt de helderheid verlaagd totdat het minimale niveau donker is ingesteld Houdt men het bedienelement dan nog ingedrukt dan wordt de helderheid weer vergroot tot maximumstop Uitschakelen Bedienelement aantip...

Page 38: ...ment van de nevenpost bedienen Alle memory tipstuurapparaaten STD MTS worden via de nevenpost tegelijkertijd bediend De inbouwdelen worden als volgt gesynchroniseerd Houd het bedienelement van de nevenpost ca 10 s ingedrukt de lichtbronnen worden op de max helder heidswaarde ingesteld en zijn vervolgens synchroon te bedienen ...

Page 39: ...etspanning Uit Aan minimale helderheid te hoog ingesteld steldezeopnieuwin Aangesloten lichtbron stuurspanning 1 V 10 V brandt niet kortgesloten schakel netspanning Uit Aan minimale helderheid te laag ingesteld stel deze opnieuw in vervang voorgeschakelde veiligheid vervang defecte fluores centielamp vervang EVSA vervang defect stuurapparaat ...

Page 40: ...Hz Corrente nominale 4 A cos ϕ 0 9 oppure 3 A cos ϕ 0 5 Potere di rottura 700 VA Potenza assorbita 1 W Entrata apparecchio derivato 230 V 10 50 Hz Tensione di comando 1 V 10 V Corrente di comando max 50 mA CC Temperatura ambiente da 0 fino a 35 C ...

Page 41: ...ssimo di EVG da collegare si ricava dai dati tecnici del relativo produttore Il carico del relè non deve superare un massimo di 4 A 10 EVG Un limitatore di corrente d inserzione integrato impedisce correnti d inserzione normalmente elevate degli EVG Se si devono comandare potenze più elevate è necessario prov vedere ad una protezione esterna ATTENZIONE In caso di interventi sul dispositivo di cont...

Page 42: ...spositivo di controllo a tasti della Memory per distribuzioni viene agganciata su una sbarra normale da 35 mm ATTENZIONE L uscita di comando 1 V 10 V del dispositivo di controllo a tasti della Memory EG 7460 non è una tensione ridotta di sicurezza Avvertenze per il montaggio ...

Page 43: ...vato La tensione di ronzio non deve tuttavia supera re i 100 V di regola questo corrisponde ad una lunghezza del cavo di almeno 100 m Per una lunghezza del cavo di 100 m il numero di tasti è illimitato Se si utilizzano tasti luminosi questi vanno inseriti solo con N L illuminazione in contatto parallelo non è ammessa Le comm involontarie vengono evitate mettendo la linea di carico e quella di coma...

Page 44: ...sato nel Modo di programmazione se si porta automaticamente su un valore di luminosità minimo Regolare le luci sul valore di luminosità desiderato e rilasciare il tasto Circa 30 secondi dopo aver rilasciato il tasto il disposi tivo di controllo EG 7460 torna automaticamente sul massimo Questo è il segno che la regolazione è stata eseguita in modo appropriato Se questo non succede ripetere la regol...

Page 45: ...60 varia questo valore e all azionamento successivo si accen de con la luminosità massima non c è più nessuna funzio ne Memory Al primo azionamento il dispositivo di controllo a tasti della Memory EG 7460 comanda dal chiaro verso lo scuro e ad ogni arresto la direzione di regolazione del varialuce viene invertito Con la luminosità massima il dimmer si arresta e con quella minima cambia la direzion...

Page 46: ...scuro o più chiaro Più chiaro tenere premuto l elemento di comando Dal valore di luminosità del momento si passa ad una luminosità più chiara fino a raggiungere il valore massimo arresto al massimo Più scuro tenere premuto l elemento di comando Dal valore di luminosità del momento si passa ad un valore più scuro fino a rag giungere il valore di luminosità minimo buio Se si continua a tenere premut...

Page 47: ...vato Tutti i dispositivi di controllo a tasto della Memory EG 7460 sono comandati e regolati con varialuce nello stesso momento per mezzo dell apparecchio derivato Gli impianti di illuminazione si possono azionare anche con un valore di luminosità uniforme Tenere premuto per circa 10 secondi l elemento di comando dell apparecchio derivato Gli impianti di illumi nazione sono messi sul valore di lum...

Page 48: ...dere la tensione di rete La luminosità minima è im postata troppo alta eseguire una nuova regolazione La luce non si accende La tensione di comando 1 10 V è in cortocircuito Spegnere accendere la tensione di rete La luminosità minima è im postata su una valore troppo basso eseguire una nuova regolazione Sostituire il dispositivo di protezione inserito a monte ...

Page 49: ...I Diagnosi Causa rimedio La luce non si accende Sostituire la lampada fluorescente difettosa Sostituire l EVG Cambiare il dispositivo di controllo difettoso Aiuto in caso di guasti ...

Page 50: ...I ...