E K I P E - H U B  

G E T T I N G  S TA R T ED

•  Up to 8 channels of analog input are sup-

ported. Channels 0 to 3 are for current input, 
and channel 4 to 7 are for voltage input.  
The channel type can be set according to dif-
ferent current/voltage ranges. 

•  Up to 8 channels of digital input are sup-

ported. Pulse meter and O/C contact can be 
selected for different DI types. 

•  All the AI and DI are set to OFF as default. 
•  It is possible to provide multiple Ekip E-Hubs 

in one installation 

•  Data logging time and data refresh on the 

web app is 30 seconds. 
However, performance could decrease if a 
large number of devices (typically more than 
30 devices, including Modbus TCP connected 
devices) are connected to ABB Ability EDCS by 
means of a single Ekip E-Hub. 

 
Also, the type of devices that are connected 
and the communication protocol used can af- 
fect  performance. To ensure high data logging 
performance, ABB suggests using more than one 
Ekip E-Hub when more than 15 devices are to be 
connected via Modbus RS-485.

Internet connection and data traffic

The Ekip E-Hub module must be provided with 
an internet connection via the site network 
(i.e., LAN) or a dedicated router with SIM card.
For an internet connection via router with SIM 
card, please consider the following sugges-
tions on the router: 
•  ABB ARG600 wireless gateway 
•  ABB ARP600 wireless gateway 

Regarding internet data traffic via mobile net-
work, it depends on the number of connected 
devices as well as on the telecom operator. 

The estimated data traffic per connected de-
vice amounts to 20GB per year.

Configuring the system

The system configurations before provisioning 
consist of four parts: Ekip E-Hub configura-
tion, field device configuration, network con-
figuration and laptop configuration.

Ekip E-Hub Configuration:

•  Ekip E-Hub LAN1 does not need a static IP ad-

dress. The default configuration is DHCP client. 

•  The Ekip E-Hub LAN2 default configuration is 

DHCP server with the following parameters:

 - Force Static IP Address: ON 
 - Static IP address: 10.86.92.1 
 - Static Subnet mask: 255.255.255.0 
 - DHCP Server IP Begin: 10.86.92.100 
 - DHCP Server IP Range End: 10.86.92.255 

 - Enable DHCP Server: ON 

Note:

If there is already one DHCP server on the LAN2, please be sure 
to disable the existing DHCP server or disable the option “En- 
able DHCP Server of Ekip E-Hub” via Ekip Connect 3  to 
avoid conflict. If you connect LAN2 to an existing DHCP server, 
internet connection should be guaranteed during the provision- 
ing procedure. Contact your network administrator to confirm.

 

•  For the configuration of the digital input and 

analog input of Ekip E-Hub, please refer to the 
kip Connect 3 – Wizard section

Field Device Configuration:

•  For connection via Modbus TCP, the down-

stream devices in the TCP network must be 
configured with the following parameters:

 - Static IP address: ON
 - Static IP address:  select an address in the 

10.86.92.2 … 10.86.92.99 range

 - Subnet mask: 255.255.255.0
 - Gateway: 10.86.92.1

Network Configuration:

•  Ekip E-Hub must be provided with an internet 

connection via either a site network or a dedi-
cated router with SIM card. 

•  For internet connectivity, you must ensure that 

the following ports are open: needed for the up-
load of the data via HTTPS  

 - 53/UDP: needed for public DNS if needed to 

use NTP server synchronization time

•  Ekip Connect uses some local ports for data 

communication with the device: 

 - Port 502 TCP, Modbus TCP Communication 
 - Port 69 UDP, TFTP Communication 

Laptop Configuration:

•  Register on 

MyABB

 to activate an account.

•  The user is not blocked by any Firewall, Device 

or Software from reaching  

https://stsint.abb.com

 on port 443 

•  The user also will need access on port 443 to the 

application or service being accessed.

•  Ensure that   the user is generally able to con-

nect to the internet and reach other internal (if 
connected to ABB Network) or external internet 
websites. 

•  Ensure that the user has cookies enabled in the 

browser.

Summary of Contents for Ekip E-Hub

Page 1: ...d LOW VOLTAGE Ekip E Hub Getting started Independent internet of things IOT gateway Up to 15 Modbus RS 485 devices can be connected Up to 8 channels of digital input are supported Up to 8 channels of...

Page 2: ...1 EKIP E HUB GETTING STARTED...

Page 3: ...Table of contents 03 06 Ekip E Hub The architecture 07 13 Ekip Connect 3 Wizard 2 TABLE OF CONTENT...

Page 4: ...Ekip Connect 3 0 346 0 and above Ekip E Hub Architecture Ekip E Hub is an independent internet of things IOT gateway that can gather data relating to field devices and the consumption of water gas et...

Page 5: ...tinuously ensure a secure con nection between the product and the customer network or any other network The customer is required to establish and main tain any appropriate measures including but not l...

Page 6: ...n is DHCP client The Ekip E Hub LAN2 default configuration is DHCP server with the following parameters Force Static IP Address ON Static IP address 10 86 92 1 Static Subnet mask 255 255 255 0 DHCP Se...

Page 7: ...already provisioned to an ABB Ability EDCS plant is allowed only for updating the plant s devices configuration e g when you need to add a new device to the EDCS plant To create a new plant you will...

Page 8: ...502 TCP Modbus TCP Communication Port 69 UDP TFTP Communication Note While the devices provisioning process is running into ABB Ability EDCS be sure your firewall is properly configured according to a...

Page 9: ...nformation and you can edit the device tag name as shown by the arrow Click Save after editing the device tag name Ekip E Hub Configuration Click Configuration then click the SNTP tab to configure the...

Page 10: ...to the Ekip Connect 3 home page 1 Click Activate 2 Click Select to access to ABB Ability EDCS Insert your myABB credentials or the login credentials you initially created on page 5 and click continue...

Page 11: ...nual Discovery is recommended On the new page select Manual Discovery settings Click on the Sniff gratuitous ARP packets box Key in the device IP address of the Ekip E Hub Module and click on the plus...

Page 12: ...d data to the ABB Abil ity EDCS Note at least one Main or Generator device must be set inside a plant Once all the settings on each device have been completed click on Add to ABB Ability EDCS You can...

Page 13: ...and renews the license Moreover this individual can edit and view everything inside ABB AbilityTM EDCS If you are the owner of the plant select Become Owner otherwise insert the email address of the...

Page 14: ...a quarter hour communication issues may exist between the field network and the cloud platform i e the UDP 53 port is not open Ekip Connect will open the default internet browser automatically and ac...

Page 15: ...14...