14. Clean finger assemblies, if necessary, with a clean, lint-free rag and isopropyl alcohol or
acetone.
15. Be sure to apply a thin film of Mobilgrease 28 (DS50HD38) to the contact areas which slide
on to the switchgear stabs . This product is available in a 1-0z tube, ABB Part #193A1751P1.
Refer manual 2TSA451015P0000
c) Remove the upper barrier.
d) Detach the inboard end of the fuse by removing the two 1/2 inch - 13 bolts. A ratchet
and socket with a short extension will be requied.
e) Remove the fuse.
f) Install the new fuse by reversing the disassembly procedure. Ensure that the mating faces
of the fuse are clean.
Figure 74
300 THRU 600 AMP CLASS J FUSE MOUNTING
ADAPTER BARS (COPPER)
73
C