L3447
Emax DC
66/108
L3728
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
13.4.4 Default settings
The PR123/DC is supplied by ABB SACE with the following predefined parameters (Set A and Set B):
#
Protection
On/Off
Thresholds
Time
Curve
T.M.
ZS
Trip
1
L
--
1 In
102s
I
2
t
Off
--
--
2
S
Off
6 In
50 ms
K
--
Off: 0.04 s --
3
I
On
4 In
--
--
--
--
--
4
G
Off
0.2 In
0.4 s
K
--
Off: 0.04 s On
5
U
Off
50 %
5 s
Off
6
OT
--
Off
7
K LC1
Off
50 % I
1
8
K LC2
Off
75 % I
1
9
UV
Off
0.9 Un
5 s
Off
10
OV
Off
1.05 Un
5 s
Off
11
RP
Off
- 0,1 Pn
10 s
Off
12
Language
--
Engl
13
PR021/K
Off
14
Measuring module type
--
HIGH VOLTAGE
15
Rated Voltage
--
500V
16
S startup
Off
6 In
100 ms
17
I startup
Off
4 In
100 ms
18
G startup
Off
1 In
100 ms
19
Password
--
0001
20
Measuring interval
--
60 min
21
Iw
Off
3 In
22
MCR
Off
6In
40 ms
--
--
--
--