8.3.5. Mechanical control
- Clean at the points indicated in figure 35. For excessive deposits, a dilutant such as Henkel 273471 or the equivalent can be used.
- Lubricate, at the points indicated in fig. 35, the opening-closing shafts and hooks with MOBILGREASE 28 (EXXON MOBIL).
- Check that the opening and closing shafts are free to rotate.
SACE PR122/V
F
Fig. 35
8.3.6. Electrical and mechanical accessories
- Check that the accessories are fixed to the circuit-breaker
- Check that the electrical accessories are connected to the circuit-breaker
- Reduction gear: after 10000 operations check brushes for wear and replace the reduction gear if necessary.
- Check that the releases (SOR-UVR-SRC) are in good condition (no excessive wear, overheating, breakages) Fig. 36.
- Check that the mechanical operation counter is operating correctly (if applicable) by running an operation on the circuit-breaker.
SACE
PR12
2/VF
SACE
PR12
2/VF
Fig. 36
8.3.7. Protection releases
- Supply the protection release from a PR030/B battery unit.
- Check that the protection release is working correctly: run “Trip Test” and “Autotest” for release.
- Use release PR122/VF to check that there are no alarms on the display and via front LEDs.
- Check that the cables are correctly connected to the release modules and to the release (if applicable).
- On PR122/VF check the wear percentage to the circuit-breaker contacts.
- At the end, remove the battery unit PR030/B from the relay.
8.3.8. Test with Ekip Connect (optional)
- Connect Ekip T&P unit on a PC and the cable adapter to the relay to be tested.
- Run the Ekip Connect software on the PC .
- Once the connection between the relay and PC has been installed, check that there are no alarm signals from the relay; otherwise,
consult the paragraphs ‘Error Messages’ and/or ‘Troubleshooting’ in this manual.
- In normal operating conditions the trip test and the autotest can be run (depending on the type of relay); for future checks, we advise
inserting the current date in the User Data and/or Tag Name area. These data will be stored inside the relay.
-
Remove the Ekip T&P cable adapter from the relay.