B2342
Emax VF
7/66
Doc. No
Model
Apparatus
Scale
Page No
1SDH000909R0001
2. Checking on receipt
Examine the state of the material received and its consistency with the content of the order. Should any damage or errors be found
on unpacking, which must be carried out carefully, make the relative notification within and not over 5 days from the receipt of the
material. The notification must indicate the number of the shipping note.
3. Storage, lifting and weights
The circuit-breaker, protected by an external wooden crate, is fixed by means of screws to the transport pallet or to the bottom of
the packing case.
If the circuit-breaker has to remain in the warehouse even for a short time before being put into service, after checking it on receipt,
it must be put back in its container and covered with a waterproof sheet.
CAUTION:
-Use a dry, dust-free room free of aggressive chemical agents as a storage room,
-Position the circuit-breaker and any fixed part on a horizontal surface, not in direct contact with the floor,
but on a suitable support surface (Fig. 5);
-The maximum number of stackable circuit-breakers is indicated in figure 6.
-Keep the circuit-breaker in the open position and with the closing springs unloaded to avoid unnecessary stresses
and the risk of accidents to the person.
-Storage temperature: -40°C … + 70°C
Fig. 5
Fig. 6
With regard to lifting, follow the instructions: the circuit-breakers must be placed on a sturdy supporting surface and lifted, preferably,
by means of a special fork-lift truck. However, the use of ropes is allowed. In this case, the lifting ropes must be hooked up as shown
in the figures (the lifting plates are always supplied with the circuit-breaker).
Fig. 7
Table of the circuit-breaker weights (Kg.)
Selective
circuit-
breaker
Fixed
version
Withdrawable
version
E2
50
78
E3
66
104
Notes:
• The weights indicated in the table are intended
for circuit-breakers complete with PR122/VF
release, excluding the accessories.
• The withdrawable version includes the moving
part in the same conditions as above, and the
fixed part with horizontal rear terminals.