Endura AZ series integral and remote transmitter
Combustion oxygen monitor
5 Programming
IM/AZ20E–EN Rev. F
39
…Calibrate
…AutoCal Hardware
Selects the type of automatic calibration hardware to be
used.
Valve Manual Control
The automatic calibration solenoid valves can be
energised manually. The current % O
2
value is shown for
reference. When this frame is exited the valves return to
the closed state.
Note
. Pressing
opens the valve; pressing
closes the valve.
A valve open / closed icon is displayed to indicate valve
status:
Test Gas 1 Valve
Disabled if
AutoCal Hardware
/
Hardware Type
is set to
None
.
Closed
Test Gas 2 Valve
Disabled if
AutoCal Hardware
/
Hardware Type
is set to
None
.
Closed
Scheduled Cal.
If AutoCal is fitted, automatic calibrations can be set to
run at scheduled time intervals.
Note
. This option is not available if the
AutoCal
Hardware
/
Hardware Type
is set to
None
.
Type
Selects the scheduled calibration type.
One point
Offset only calibration.
Two point
Offset and cal factor calibration.
Two point
Frequency
Selects the frequency of automatic calibrations.
Off
Disables scheduled calibrations.
Off
Daily
Enables the
Daily Interval
parameter.
Weekly
Enables the
Weekly Interval
parameter.
Monthly
Enables the
Monthly Interval
parameter.
Parameter
Comment / [Range]
Default
Table 5.7 Calibrate Menu (Continued)
Valve Open
Valve Closed