Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
13 Transmitter Specification
COI/AZ30E–EN Rev. D
105
Threaded entries
Gland entries (certified):
Pneumatic entries (not certified):
4 fittings supplied with AutoCal options or 3 fittings and 1 blanking plug supplied with non-AutoCal options. Size
options:
1
/
4
in BSP for 6 mm OD pipe (with M20 cable gland option) or
1
/
4
NPT for
1
/
4
in OD pipe (with
1
/
2
NPT option)
Automatic Calibration
AutoCal hardware
Isolated solenoid valve control as standard, 24 V @
2 W per valve*
Dedicated isolated digital inputs to monitor pressure switch contacts as standard:
voltage-free, normally closed with gas present
*For driving internal automatic calibration (AutoCal) probes or can be used to drive external automatic calibration units on
remote transmitters only.
Display and Switches
Display type
Graphical 128 x 64 pixel LCD
Display backlight
Green LED
Operator switches
4 capacitive switches (operated through the front glass)
Relay Outputs
Number
2 standard
Type
Normally closed 5 A @ 230 V AC or 30 V DC (non-inductive)
Functions
User-configurable – can be activated by one or more of the following signals:
Process alarm 1, 2, 3, 4
Calibration in progress
Calibration failed
Out of test gas 1, 2
Test gas 1 valve control
Test gas 2 valve control
Failure diagnostic
Out-of-specification diagnostic
Maintenance required diagnostic
Function check diagnostic
Power and signals gland entries:
3 x M20 or (optional)
1
/
2
in NPT
Remote terminal housing cable gland entry:
1 x M25 or (optional)
3
/
4
in NPT (remote system only)