1SDH000510R0001
11/28
Page N.
L2388
EP010
ABB SACE
Table 5. Normal LEDs behaviour
(1) If the FBP is disconnected, the EP010 is powered off.
After a failure has been detected and signalled, the FAULT LED continues flashing until:
1 the FBP is communicating with the EP010 (and then the EP010 is communicating with the
device using the Modbus port) and the fault is removed OR
2 the EP010 id powered off (i.e. the FBP is disconnected) or reset.
While in run state, EP010 can be in one of the following conditions:
1 FBP communicated with EP010, connected Modbus device responding (see 2.8.2.2): this
is the normal working condition
2 FBP not communicating (see 2.8.2.1)
3 FBP communicates, device not responding (see 2.9).
2.8.2.1 Communication with the FBP
Status of the communication between EP010 and FBP is indicated by FBP green LED:
flashing means communication is working, OFF means no communication.
2.8.2.2 Communication with the Modbus device
EP010 works by polling the connected device, i.e., sending Modbus telegrams (queries) to the
Modbus device and receiving responses (response telegrams) from it.
Modbus RTU query sending from EP010 to device is started when the FBP communication
between the FBP and the EP010 is started.
Modbus RTU communication between EP010 and the device (i.e. stop query sending) is stopped
when the communication between the FBP and the EP010 is stopped.
EP010 considers Modbus device to be “disconnected” when there is a checksum (CRC) error
in a response telegram, or there is no response after 4 attempts (retries) to send the same .
query. When this appens, EP010 stops asking the device for data, and it starts sending probe
queries (“Report Slave ID”) to check when the device resumes communication, then starts .
polling data again.
When the communication between the EP010 and the device fails, the EP010 .
data are neither updated not reset: they are frozen until the communication has
been restored.
2.8.3 Command interface
It’s possible to issue a command to the EP010 using two different interfaces:
1 cyclic, realized with an Analog Input process variable
2 acyclic, realized with a Parameter (parameter number 1)
LED
Color
ON
OFF
FLASHING
RX
Green
FBP doesn’t communicate with EP010
FBP communicates AND
OR no response from PU
Modbus response from PU
(if TX flashes)
receiving
FAULT Yellow
See 2.9
FBP
Green
FBP doesn’t communicate with EP010
FBP communicates with EP010