1SDH000510R0001
19/28
Page N.
L2388
EP010
ABB SACE
31 Wink ON
OFF | ON
0 | 1
32 Signalling Module Input Status
Not active | Active
0 | 1
33 KK function
OFF | ON
0 | 1
34 Waveform session status
1 = Busy
Yes
35 Harmonic distortion > 2.1
36 Contact Wear Pre-alarm
37 Contact Wear Alarm
38 L pre-alarm
39 L Timing
40 S Timing
41 S2 Timing
Yes
42 G Timing
43 G Alarm (Blocked Trip)
44 G Ext Timing
45 G Ext Alarm (Blocked Trip)
46 T Pre-alarm
47 T Alarm
48 T Alarm (Blocked Trip)
49 D Timing
Yes
50 U timing
51 U Alarm (Blocked Trip)
52 UV timing
53 UV Alarm (Blocked Trip)
54 OV Timing
55 OV Alarm (Blocked Trip)
56 RV Timing
57 RV Alarm (Blocked Trip)
58 RP Timing
59 RP Alarm (Blocked Trip)
60 UF Timing
61 UD Alarm (Blocked Trip)
62 OF timing
63 OF Alarm (Blocked Trip)
64 Frequency Error
65 Iw Warning
66 LC1 Alarm
67 LC2 Alarm
68 L1 Sensor error
69 L2 Sensor error
70 L3 Sensor Error
71 N Sensor Error
72 GTe Sensor error
73 SA Error
74 Rating Plug Error
75 Key Plug Error
76 Temperature Sensor Error
77 Power Factor Error
78 Phase Cycle Error
79 Invalid Date
80 Configuration Error
81 CB Status Erroe
82 local bus Relè 1 contact
Open | Closed
0 | 1
83 local bus Relè 2 contact
Open | Closed
0 | 1
84 local bus Relè 3 contact
Open | Closed
0 | 1
85 local bus Relè 4 contact
Open | Closed
0 | 1
86 NOT USED
87 local bus Relè 6 contact
Open | Closed
0 | 1
88 local bus Relè 7 contact
Open | Closed
0 | 1
89 local bus Relè 8 contact
Open | Closed
0 | 1
90 Relè P1 contact
Open | Closed
0 | 1
91 Relè P2 contact
Open | Closed
0 | 1
92 Relè P3 contact
Open | Closed
0 | 1
93 Relè P4 contact
Open | Closed
0 | 1
94 S zone selectivity input
1 = input active
95 S zone selectivity output
1 = output active
96 G zone selectivity input
1 = input active
97 G zone selectivity output
1 = output active
98 L tripped
99 S tripped
100 S2 tripped
Yes
101 I tripped
102 Iinst tripped
103 G tripped
104 G ext tripped
105 T tripped
106 D tripped
Yes
107 UN tripped
108 UV tripped
109 OV tripped
110 RV tripped
111 RP tripped
112 UF tripped
113 OF tripped
114 Electronic Trip Test
115 Simulated Trip from Test Unit
116 External Input Trip
117 Hardware error Trip
118 NOT USED
119 NOT USED
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default