2.6
Technical data
2.6.1 General data
Total dissipation max.
432 mW
Conductor cross section of the connection terminals
max. 2.5 mm
2
2.6.2 Power supply for EP010
Supply voltage
24 V DC via field bus plug
Current consumption
via field bus plug max. 18 mA
2.6.3 Connection of the FieldBusPlug
Mounting
Plug connection, fastening with supplied screw
Suitable ABB filed bus plug types
DeviceNET yes
PROFIBUS DP yes
EP010 supports only the “long serial protocol” to communicate with the FBP.
Therefore, the AS-i P and AS-i Fieldbus Plugs cannot be used with the EP010.
When a Profibus FBP is used, the EP010 GSD file associated to the connected device is
required.
When a deviceNet FBP is used, the relevant EP010 EDS file associated to the connected
device is reqiuired.
They can be downloaded from the ABB web site.
2.6.4 Connection to a Modbus device
Device communication parameters have to be:
Table 3. Device communication parameters
Slave Address
247(0xF7)
Baudrate
19200
Parity
Even
Stop bits
1
Addressing Type (where applicable)
Standard