The ESI-Manager user interface 103
Figure 73: Example of the Min/Max logging function (4-W mode)
7.9 The ‘Settings’ menu
The ‘Settings’ menu [/Welcome/Settings] has four main levels:
−
The customer level which allows the user to set up the typical user requirements
such as the active and reactive power set points, harmonic filtration settings,
sets up the digital inputs and outputs and defines the programmable warnings
and alarms. At this level, the user can also change the temperature unit used by
the system. The customer level is accessed through
[/Welcome/Settings/Customer set.]
−
The commissioning level which allows the commissioning engineer to set up the
equipment according to the customer’s installation. Typical parameters that
need to be entered are the network voltage and frequency, the CT parameters
and a derating factor that needs to be applied when the installation is at great
height above sea level or in conditions where excessive ambient temperatures are
present. At the commissioning level the possibility also exists to set up the user’s
requirements for the power control (AC or DC target), set up the LVRT settings,
harmonic filtration and reactive power compensation. The commissioning level is
accessed through [/Welcome/Settings/Commissioning].
−
The installation settings level allows for the commissioning engineer to set up
advanced system functions such as the inverter auto restart and standby