12 Technical specifications
12.1 What this chapter contains
This chapter contains the technical specifications of the inverter ESI-S.
12.2 Technical specifications
The ESI-S is an inverter for three phase networks with or without neutral for filtering of
non-zero-sequence and zero-sequence harmonics and reactive power compensation
including balancing between phases.
Table 64: Technical Specifications
Installation location
Indoor installation on firm foundation mounted in a clean environment
Altitude
Nominal output at 0 to 1000m (3300ft) above sea level (for
derating refer to
Minimum temperature
-10°C (23°F) non condensing
Maximum temperature
40°C (104°F) (for derating refer to
Recommended maximum average
temperature (over 24 h)
35°C (95°F)
Relative humidity
Max. 95% non-condensing.
Contamination levels (IEC 60721-3-3)
Chemical class 3C2 (for more information refer to
Mechanical class 3S2 (for more information refer to
Table
15
Vibration (IEC 60068-2-6)
Max. 0.3mm (2-9Hz)
Max. 1m/s
2
(9-200Hz)
Shock (IEC 60068-2-27)
Max. 40m/s² - 22ms
Inverter installation information
Degree of protection
IP30
Dimensions per power unit enclosure
(appr.)
W x D x H: 588 x 326 x 752 mm
W x D x H: 588 x 326 x 795 mm (including fixations)
Weight per power unit enclosure
(unpacked)
130 kg
Color
RAL 7035 (light gray).
Mechanical installation
Wall mounted (fixation plates included)
Cable entry method
Bottom cable entry
CT requirements
Only required for Power Quality features
Airflow requirements
A minimum airflow of cooling air has to be supplied to each
cubicle:
30A - 60A: 520 m³/h
70A - 100A: 520 m³/h