When mounting the units in existing metal panels or
enclosures, ensure that the enclosure is securely bonded
to the earth bar to which the ESP unit will be connected.
If it is not possible to install the unit within the
distribution panel it should be mounted in a separate
enclosure,
see Figure 2
, as close as possible to the
distribution panel (
see 3.9 - Length of connecting leads
).
Gland the enclosure onto the power distribution panel.
Suitable enclosures are available from Furse.
3/3
| Installation instructions for mains wire-in protectors
NO
Volt free contact
ESP
240 M1
STATUS INDICATION
ELECTRONIC SYSTEMS
PROTECTION
Made by W J Furse & Co Ltd, ESP Division,
Wilford Road, Nottingham, NG2 1EB, UK
L
L N
L
1
N
N
WARNING
PATENT
APPLIED
FOR
If lit / flashing disconnect
unit & check Neutral to
Earth supply voltage
NC C
GREEN
FULL PROTECTION
NO PROTECTION
REDUCED PROTECTION
(replace unit)
GREEN & RED
RED
Let-through voltage
600V
1 phase/50Hz
(Live to Neutral, Live to Earth & Neutral to Earth)
Vmax 280Vrms
Figure 3: Parallel
connection for single
phase supplies.
To
load
From
supply