Fig. 1b
A Circuit-breaker rating plate
B Sensor rating plate
C Operating mechanism rating plate
D Configuration code
1 Type of apparatus
2 Symbols of compliance with Standards
3 Serial number
4 Circuit-breaker characteristics
5 Characteristics of the operating mechanism
auxiliaries
2. Checking on receipt
Before carrying out any operation, always make
sure that the spring of the operating mechanism
is released and that the apparatus is in the open
position.
On receipt, immediate check the condition of the packing and
the color of the “SHOCK WATCH” (fig. 1a) impact indicator..
If the “SHOCKWATCH” impact indicator is RED, follow the in-
structions indicated on the plate.
Opening the packing does not damage its components, therefore
it can be remade using the original material supplied.
Also make sure that all the materials described in the shipping
note are included in the supply.
Should any damage or irregularity be noted in the supply
on unpacking, notify ABB (directly or through the agent or
supplier) as soon as possible and in any case within five days
of receipt.
The apparatus is only supplied with the accessories specified
at the time of ordering and validated in the order confirmation
sent by ABB.
The accompanying documents included in the shipping
packing are:
– instruction manual (this document)
– test certification
– identification label
– copy of the shipping documents
– electric wiring diagram.
Other documents which are sent prior to shipment of the
apparatus are:
– order confirmation
– original shipping advice note
– any drawings or documents referring to special
configurations/conditions.
CIRCUIT-BREAKER
eVD4/P 12.06.25
CLASSIFICATION M2
SN 1VC1BA00045139
M WEIGHT
124
kg
Ur VOLTAGE
12
kV
Up LIGHTNING IMPULSE WITHSTAND VOLTAGE
75
kV
Ud POWER FREQUENCY WITHSTAND VOLTAGE
28
kV
fr
FREQUENCY
50/60
Hz
Ir
THERMAL CURRENT
630
A
A
lk
SHORT TIME WITHSTAND CURRENT
25
kA
tk
DURATION OF SHORT CIRCUIT
3
s
ISC BREAKING CURRENT
25
kA
MAKING CAPACITY (PEAK VALUE)
63
kA
AT THE VOLTAGE OF
12
kV
D.C. COMPONENT
< = 30
%
Ic BREAKING CURRENT FOR NO-LOAD CABLES
25
A
OPERATING SEQUENCE O-0,3S-CO-15S-CO
CURRENT SENSOR
IPR:250A CL: 1/5P
KEVCR 17.5 AC1
USR: 0.150/0.180V
EL1 OPERATING MECHANISM
ELECTRICAL DIAGRAM 1VCD400106 (V2970)
FIG. 01 FIG. 56 FIG. 66 FIG. 70 FIG. 75
CONFIGURATION CODE: XAAWILANLNC1
IEC 62271-100
CEI 17-1
IEC 60044-7, -8
IEC 60255-26
PR. YEAR 2010
-MBC -MBO1 -RLE2 -AA 24 ... 60 V
-MAS 220 V
50Hz
RBX615
CONFIGURATION CODE: XAAWILANLNC1
Made by
ABB Italy
Impact indicator
When the “SHOCKWATCH” impact indicator is WHITE it means
that the packing has not sustained any serious shock during
transport. Open the packing, check the condition of the ap-
paratus and correspondence of the nameplate data (see fig.
1b) with the data specified in the shipping note and in the order
acknowledgement sent by ABB.