GUID-CD8CF7D5-18A7-460C-8AAD-60DB73F9DBCB V1 EN
Figure 18:
Confirming a GOOSE input deletion
3.
To update the data flow, select
Tools/IEC61850 Data Flow Engineering/
Update DataFlow
.
5.3.6
Finalizing GOOSE configuration
5.3.6.1
Exporting the SCL file
1.
Click
Tools/SCL Import/Export/Export SCL File
.
GUID-52150B11-1100-4D0F-83F4-6E44BECEC7BF V1 EN
Figure 19:
Exporting an SCD file
2.
Click
Browse
to select the file destination and click
OK
.
The tool proposes its project location for the SCD file, and it is recommended
to leave the SCD file exported from PCM600 as a backup.
3.
In
FormSclExportDialog
, select the
Suppress Private CCT Type
Information
check box.
PCM600 does not require private CCT type information.
Section 5
1MRS757255 B
GOOSE
32
Breaker Integrated Protection RBX615
Engineering Guide